Unit: inch (mm)
Unit Type a b
006 to 012 5-7/8 (150) 3-15/16 (100)
015 to 030 3-15/16 (100) 7-7/8 (200)
(1) Install the indoor unit with recommended clearances
around it for proper operation, maintenance working
space and safety, as shown in the illustration at right.
4. Installation Location
(2) Consider the air distribution from the indoor unit to the space of the room, and select a suitable location
so that uniform air temperature in the room can be obtained.
(3) Install the unit where there are no obstacles such as electric lights or a partition, which can impede the
suction air and discharged air.
In the case of using a wireless controller, avoid installing the indoor unit to within approximately
3.3ft (1m) from electronic type lighting so that the signal remains unaffected when transmitted to the
receiver.
(4) Check to ensure that the wall is able to withstand the weight of the indoor unit. If there is insufcient
structural integrity, noise in the form of vibration generated by the unit is magnied.
(5) Verify that the supporting walls are vertical and at.
(6) Install the indoor unit as high off the oor as possible.
If not, airow distribution will be affected and these effects will cause discomfort to some people.
(7) Do not install the unit near a door or ceiling where the indoor unit comes into contact with humid outside
air. Otherwise, condensation may occur.
(8) Do not install the indoor unit where airow from the air outlet blows directly onto temperature sensing
devices such as an alarm device or a control device. This can result in false readings and an alarm
failure.
Vertical Airflow
As High as Possible
(Min. 94-1/2 inches (2400mm))
Horizontal Airflow
Min.
a
Min.
b
Min.
38-3/8
(1000)
Min.
3-15/16
(100)
Unit: inch (mm)
Obstacles
NOTE:
When connecting the wall mount type indoor unit to the VRF system, consider the installation location of the
optional strainer kit.