JOHNSON CONTROLS
28
Ratings - R-407C (English Units)
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certied in accordance with ARI Standard 550/590-98
YCAL0094EB
IPLV=13.4
YCAL0090EB
IPLV=13.6
YCAL0080EB
IPLV=14.4
YCAL0074EB
IPLV=14.2
AIR TEMPERATURE ON CONDENSER (°F)
LCWT
(°F)
75°F 80°F 85°F 90°F 95°F 100°F
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
40.0
75°F 70.1 11.7 72.9 74.4 10.8 70.8 79.0 9.9 68.7 83.8 9.1 66.5 88.9 8.3 64.3 94.3 7.6
42.0
77.7 70.8 12.0 75.7 75°F
11.1 73.5 79.6 10.2 71.3 84.5 9.4 69.0 89.6 8.6 66.8 95.0 7.9
44.0
80.6 71.4 12.4 78.4 75.7 11.4 76.2 80.3 10.5 73.9 85.2 9.6 71.6 90.3 8.8 69.3 95.8 8.1
45.0
82.0 71.8 12.5 79.8 76.0 11.6 77.6 80.6 10.6 75.3 85.5 9.8 72.9 90.7 9.0 70.5 96.2 8.2
46.0
83.5 72.1 12.7 81.3 76.4 11.7 79.0 81.0 10.8 76.6 85.9 9.9 74.2 91.1 9.1 71.8 96.6 8.3
48.0
86.5 72.7 13.0 84.2 77.1 12.0 81.8 81.7 11.1 79.4 86.7 10.2 76.9 91.9 9.4 74.4 97.4 8.6
50.0
89.5 73.5 13.4 87.1 77.9 12.3 84.7 82.5 11.4 82.2 87.5 10.5 79.7 92.7 9.6 77.1 98.3 8.8
AIR TEMPERATURE ON CONDENSER (°F)
LCWT
(°F)
75°F 80°F 85°F 90°F 95°F 100°F
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
40.0
81.6 77.5 11.6 79.4 82.3 10.7 77.2 87.3 9.8 74.9 92.7 9.0 72.6 98.2 8.3 70.2 104.2 7.6
42.0
84.6 78.3 11.9 82.4 83.0 11.0 80.0 88.1 10.1 77.7 93.4 9.3 75.3 99.1 8.5 72.8 105.1 7.8
44.0
87.7 79.0 12.3 85.3 83.8 11.3 82.9 88.9 10.4 80.5 94.3 9.6 78.0 100.0 8.8 75.5 106.0 8.0
45.0
89.2 79.4 12.4 86.8 84.2 11.4 84.4 89.3 10.5 81.9 94.7 9.7 79.4 100.4 8.9 76.8 106.5 8.1
46.0
90.8 79.8 12.6 88.3 84.7 11.6 85.9 89.7 10.7 83.4 95.2 9.8 80.8 100.9 9.0 78.2 107.0 8.3
48.0
93.9 80.6 12.9 91.4 85.5 11.9 88.9 90.6 11.0 86.3 96.1 10.1 83.7 101.8 9.2 81.0 107.9 8.5
50.0
97.2 81.4 13.2 94.6 86.3 12.2 92.0 91.6 11.2 89.3 97.0 10.3 86.6 102.8 9.5 83.8 109.0 8.7
AIR TEMPERATURE ON CONDENSER (°F)
LCWT
(°F)
75°F 80°F 85°F 90°F 95°F 100°F
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
40.0
82.5 72.8 11.8 80.4 76.8 11.0 78.2 80.9 10.2 76.0 85.4 9.5 73.6 90.2 8.7 71.2 95.4 8.0
42.0
85.7 73.4 12.2 83.6 77.4 11.4 81.3 81.6 10.6 79.0 86.0 9.8 76.6 90.8 9.0 74.1 96.0 8.3
44.0
89.1 74.0 12.6 86.8 78.0 11.7 84.5 82.2 10.9 82.1 86.7 10.1 79.6 91.5 9.3 77.0 96.7 8.6
45.0
90.8 74.3 12.8 88.5 78.3 11.9 86.1 82.6 11.1 83.7 87.1 10.3 81.2 91.9 9.5 78.6 97.0 8.7
46.0
92.5 74.6 13.0 90.1 78.7 12.1 87.7 82.9 11.2 85.3 87.4 10.4 82.7 92.2 9.6 80.1 97.4 8.9
48.0
96.0 75.3 13.4 93.5 79.4 12.4 91.1 83.6 11.6 88.5 88.2 10.7 85.9 93.0 9.9 83.2 98.1 9.2
50.0
99.4 76.0 13.7 97.0 80.1 12.8 94.5 84.4 11.9 91.8 88.9 11.0 89.1 93.8 10.2 86.3 98.9 9.4
AIR TEMPERATURE ON CONDENSER (°F)
LCWT
(°F)
75°F 80°F 85°F 90°F 95°F 100°F
TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
40.0
88.8 80.0 11.7 86.5 84.4 10.9 84.3 88.8 10.2 82.0 93.6 9.4 79.6 98.6 8.7 77.1 104.0 8.1
42.0
92.2 80.8 12.1 89.9 85.1 11.2 87.5 89.7 10.5 85.1 94.4 9.7 82.7 99.5 9.0 80.1 104.8 8.3
44.0
95.7 81.5 12.4 93.3 85.9 11.6 90.9 90.5 10.8 88.4 95.3 10.0 85.8 100.3 9.3 83.2 105.7 8.6
45.0
97.4 81.9 12.6 95.0 86.3 11.7 92.5 90.9 10.9 90.0 95.7 10.1 87.4 100.8 9.4 84.8 106.2 8.7
46.0
99.2 82.2 12.8 96.8 86.7 11.9 94.3 91.3 11.1 91.7 96.2 10.3 89.1 101.3 9.5 86.4 106.7 8.8
48.0
102.9 83.0 13.2 100.3 87.5 12.2 97.7 92.2 11.4 95.1 97.1 10.6 92.4 102.2 9.8 89.6 107.6 9.1
50.0
106.6 83.9 13.5 104.0 88.3 12.6 101.3 93.1 11.7 98.6 98.0 10.9 95.8 103.2 10.1 92.9 108.6 9.3