NOTES:
1. kWo = Unit kW Cooling Capacity Output
2. kWi = Compressor kW Input
3. COP = Coefcient of Performance (Based upon compressor and fan input kW)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based upon 0.15L/s cooler water per kW
Ratings - R-407C (SI Units)
YCAL0014EB
COP=3.69
YCAL0020EB
COP=3.79
YCAL0024EB
COP=3.86
YCAL0030EB
COP=3.98
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
47.5 11.5 3.3 45.1 12.9 2.9 41.9 14.7 2.4 39.3 16.4 2.1 37.4 17.7 1.8 18.3 9.0 1.6
6.0
49.1 11.6 3.4 46.6 12.9 3.0 43.4 14.8 2.5 40.8 16.4 2.1 38.8 17.8 1.9 19.0 9.0 1.6
7.0
50.8 11.6 3.5 48.3 13.0 3.1 45.0 14.8 2.6 42.3 16.4 2.2 39.7 18.2 1.9 19.7 9.0 1.7
8.0
52.6 11.7 3.6 49.9 13.0 3.2 46.7 14.8 2.7 43.9 16.5 2.3 41.1 18.3 2.0 20.5 9.0 1.7
9.0
54.4 11.7 3.7 51.6 13.1 3.3 48.4 14.8 2.8 45.5 16.5 2.4 42.7 18.3 2.0 21.3 9.0 1.8
10.0
56.2 11.8 3.9 53.4 13.1 3.4 50.1 14.8 2.8 47.1 16.5 2.4 44.2 18.4 2.1 22.1 9.1 1.9
11.0
57.8 12.0 3.9 54.9 13.3 3.4 51.8 14.9 2.9 48.8 16.6 2.5 45.8 18.4 2.2 22.9 9.1 1.9
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
64.6 16.9 3.3 61.2 18.9 2.8 57.7 21.0 2.4 54.4 23.4 2.1 51.1 25.9 1.8 25.8 12.6 1.7
6.0
66.8 17.0 3.4 63.3 19.0 2.9 59.8 21.1 2.5 56.3 23.5 2.1 52.9 26.1 1.8 26.8 12.7 1.7
7.0
69.0 17.1 3.5 65.4 19.1 3.0 61.8 21.2 2.6 58.2 23.6 2.2 54.8 26.2 1.9 27.6 12.8 1.8
8.0
71.3 17.2 3.6 67.6 19.2 3.1 63.9 21.4 2.7 60.2 23.8 2.3 56.7 26.4 1.9 28.7 12.8 1.8
9.0
73.7 17.3 3.7 69.9 19.3 3.2 66.0 21.5 2.7 62.3 23.9 2.3 58.6 26.6 2.0 29.7 12.9 1.9
10.0
76.1 17.4 3.8 72.2 19.4 3.3 68.3 21.6 2.8 64.4 24.1 2.4 60.6 26.7 2.1 30.8 12.9 2.0
11.0
78.6 17.5 3.9 74.5 19.5 3.3 70.5 21.8 2.9 66.5 24.2 2.5 62.6 26.9 2.1 31.9 12.9 2.0
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
80.5 21.0 3.4 76.4 23.3 2.9 72.1 25.9 2.5 67.9 28.4 2.2 63.8 31.4 1.9 31.7 15.7 1.7
6.0
83.2 21.2 3.5 79.1 23.4 3.0 74.6 26.0 2.6 70.1 28.9 2.2 65.6 31.9 1.9 32.9 15.8 1.8
7.0
86.1 21.3 3.6 81.8 23.6 3.1 77.2 26.2 2.7 72.6 29.0 2.3 68.0 32.0 2.0 34.2 15.8 1.8
8.0
89.0 21.5 3.7 84.5 23.7 3.2 79.9 26.3 2.7 75.2 29.2 2.4 70.5 32.2 2.0 35.5 15.9 1.9
9.0
91.9 21.6 3.8 87.3 23.9 3.3 82.6 26.5 2.8 77.8 29.4 2.4 73.0 32.4 2.1 36.8 16.0 2.0
10.0
94.9 21.8 3.9 90.2 24.1 3.4 85.4 26.7 2.9 80.4 29.6 2.5 75.5 32.7 2.1 38.2 16.1 2.0
11.0
98.0 22.0 4.0 93.2 24.3 3.4 88.2 26.9 3.0 83.1 29.8 2.6 78.1 32.9 2.2 39.5 16.1 2.1
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
98.5 25.6 3.5 93.7 28.6 3.0 88.8 31.8 2.6 83.8 35.3 2.2 78.6 39.2 1.9 39.4 19.3 1.8
6.0
101.9 25.7 3.6 97.0 28.7 3.1 91.9 31.9 2.7 86.7 35.5 2.3 81.4 39.4 1.9 40.9 19.4 1.8
7.0
105.4 25.9 3.7 100.3 28.8 3.2 95.1 32.1 2.7 89.7 35.6 2.3 84.2 39.6 2.0 42.4 19.5 1.9
8.0
108.9 26.0 3.8 103.7 29.0 3.3 98.3 32.2 2.8 92.8 35.8 2.4 87.1 39.7 2.1 43.9 19.5 2.0
9.0
112.5 26.2 3.9 107.1 29.1 3.4 101.6 32.4 2.9 95.9 36.0 2.5 90.1 40.0 2.1 45.5 19.6 2.0
10.0
116.1 26.3 4.0 110.6 29.3 3.5 105.0 32.6 3.0 99.1 36.2 2.5 50.4 17.7 2.5 47.1 19.6 2.1
11.0
119.9 26.5 4.1 114.2 29.5 3.5 108.4 32.8 3.1 102.4 36.4 2.6 52.1 17.7 2.5 48.8 19.7 2.2