JOHNSON CONTROLS
33
FORM 150.62-EG1 (507)
NOTES:
1. kWo = Unit kW Cooling Capacity Output
2. kWi = Compressor kW Input
3. COP = Coefcient of Performance (Based upon compressor and fan input kW)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based upon 0.15L/s cooler water per kW
COP=3.99
COP=4.02
YCAL0034EB
COP=4.13
YCAL0040EB
COP=4.18
YCAL0042EB
YCAL0044EB
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
118.0 32.5 3.3 111.8 36.2 2.9 105.4 40.1 2.5 98.9 44.4 2.1 92.5 48.9 1.8 60.8 33.4 1.7
6.0
121.8 32.8 3.4 115.5 36.5 2.9 108.9 40.5 2.5 102.3 44.8 2.2 95.7 49.3 1.8 63.0 33.5 1.7
7.0
125.8 33.1 3.5 119.3 36.8 3.0 112.5 40.8 2.6 105.7 45.1 2.2 99.0 49.7 1.9 65.4 33.7 1.8
8.0
129.8 33.5 3.6 123.1 37.1 3.1 116.2 41.1 2.7 109.3 45.5 2.3 102.4 50.1 1.9 67.8 33.9 1.8
9.0
133.9 33.8 3.7 127.1 37.4 3.2 120.0 41.5 2.7 112.9 45.9 2.3 105.9 50.5 2.0 70.2 34.2 1.9
10.0
138.1 34.1 3.7 131.1 37.7 3.2 123.9 41.8 2.8 116.6 46.3 2.4 109.4 51.0 2.0 72.8 34.4 2.0
11.0
142.5 34.4 3.8 135.2 38.1 3.3 127.8 42.2 2.8 120.4 46.7 2.4 80.4 31.4 2.4 75.3 34.6 2.0
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
134.1 32.6 3.5 125.2 37.7 2.9 120.4 40.7 2.6 113.5 45.3 2.2 106.7 50.4 1.9 52.2 25.7 1.7
6.0
138.7 32.8 3.6 129.9 37.6 3.0 124.7 40.8 2.7 117.6 45.5 2.3 110.7 50.6 2.0 53.4 25.7 1.7
7.0
143.4 32.9 3.7 134.7 37.6 3.1 129.1 40.9 2.8 121.8 45.6 2.4 114.6 50.8 2.0 56.3 25.7 1.8
8.0
148.3 33.0 3.8 139.6 37.6 3.2 133.6 41.1 2.9 126.1 45.8 2.5 118.7 51.0 2.1 58.5 25.8 1.9
9.0
153.3 33.2 4.0 144.6 37.6 3.4 136.8 42.0 2.9 130.5 45.9 2.5 122.9 51.2 2.2 60.7 25.8 1.9
10.0
158.4 33.3 4.1 149.8 37.6 3.5 141.8 42.0 3.0 133.8 46.9 2.6 127.2 51.4 2.2 62.9 25.8 2.0
11.0
163.7 33.4 4.2 155.0 37.6 3.6 146.7 42.1 3.1 138.6 47.0 2.6 130.5 52.3 2.3 65.3 25.9 2.1
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
148.6 38.5 3.4 141.1 42.8 2.9 133.3 47.7 2.5 125.4 53.0 2.1 117.6 58.7 1.8 82.4 45.1 1.6
6.0
153.0 39.1 3.4 146.0 43.1 3.0 138.0 47.9 2.6 129.9 53.2 2.2 121.9 59.0 1.9 85.5 45.3 1.7
7.0
158.3 39.3 3.5 151.1 43.3 3.1 142.8 48.2 2.7 134.6 53.5 2.3 126.3 59.3 1.9 88.7 45.4 1.7
8.0
163.8 39.4 3.6 156.2 43.5 3.2 147.7 48.4 2.7 139.2 53.8 2.4 130.8 59.6 2.0 91.9 45.7 1.8
9.0
169.4 39.6 3.8 160.9 44.0 3.2 152.1 49.0 2.8 144.0 54.1 2.4 135.4 59.9 2.1 95.2 45.8 1.9
10.0
175.1 39.8 3.9 166.3 44.2 3.3 157.4 49.2 2.9 148.9 54.4 2.5 140.0 60.3 2.1 98.6 46.0 1.9
11.0
180.9 40.0 4.0 171.9 44.5 3.4 162.7 49.5 3.0 153.5 55.0 2.5 108.3 42.0 2.3 101.6 46.6 2.0
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
163.6 42.9 3.4 155.3 47.7 2.9 146.6 52.9 2.5 137.7 58.7 2.1 128.8 64.8 1.8 64.5 32.1 1.7
6.0
169.3 43.2 3.5 160.6 48.0 3.0 151.6 53.3 2.6 142.6 59.0 2.2 133.5 65.2 1.9 66.9 32.3 1.8
7.0
175°F 43.5 3.6 166.1 48.3 3.1 156.9 53.6 2.7 147.7 59.4 2.3 138.3 65.6 1.9 69.5 32.4 1.8
8.0
180.8 43.8 3.7 171.7 48.6 3.2 162.2 54.0 2.7 152.7 59.8 2.3 143.2 66.0 2.0 72.2 32.6 1.9
9.0
186.8 44.2 3.8 177.4 48.9 3.3 167.7 54.3 2.8 157.9 60.2 2.4 148.2 66.4 2.1 74.8 32.7 2.0
10.0
192.9 44.5 3.9 183.2 49.3 3.3 173.2 54.7 2.9 163.2 60.6 2.5 153.2 67.0 2.1 77.6 32.9 2.0
11.0
199.1 44.9 3.9 189.2 49.7 3.4 179.0 55.1 3.0 168.6 61.1 2.5 158.4 67.5 2.2 80.4 33.0 2.1