FORM 150.67-EG1 (219)
JOHNSON CONTROLS
101
P. Power Factor Correction Capacitors: Provided to correct unit compressor factors to a
0.90-0.95.
Q. Condenser Coil Environmental Protection:
1. Pre-Coated: Epoxy coated aluminum n stock to guard from corrosive agents and
insulate against galvanic potential. For mild seashore or industrial locations.
2. Copper Fin: Provide copper ns in lieu of aluminum.
3. Post-Coated Dipped: Dipped-cured coating on condenser coils for seashore and
other corrosive applications (with the exception of strong alkalis, oxidizers, and wet
bromine, chlorine and uorine in concentrations greater than 100ppm).
R. Protective Chiller Panels (Factory or Field Mounted)
1. Louvered Panels (condenser coils only): Painted steel as per remainder of unit cabi-
net, over external condenser coil faces.
2. Wire Panels (full unit): Heavy gauge, welded wire-mesh, PVC-coated to resist cor-
rosion, to protect condenser coils from incidental damage and restrict unauthorized
access to internal components.
3. Louvered Panels (full unit): Painted steel as per remainder of unit cabinet, to protect
condenser coils from incidental damage, visually screen internal components, and
prevent unauthorized access to internal components.
4. Louvered/Wire Panels: Louvered steel panels on external condenser coil faces,
painted as per remainder of unit cabinet. Heavy gauge, welded wire-mesh, coated
to resist corrosion, around base of machine to restrict unauthorized access.
S. Flow Switch (Field-mounted): Vapor proof SPDT, NEMA 4X switch ( ___150 PSIG or
___300 PSIG), -20°F to 250°F.
T. Differential Pressure Switch: Alternative to an above mentioned ow switch. Pretemp-
co model DPS300A-P40PF-82582-5 (300 psi max. working pressure) SPDT 5 amp
125/250VAC switch, Range 3-45 PSIG (0.2-3 barg), deadband 0.5 - 0.8 psi, with 1/4”
NPTE Pressure Connections.
U. Evaporator options:
1. Provide 1½" cooler insulation in lieu of standard ¾".
2. Provide DX Cooler with 300 PSIG water-side design working pressure in lieu of
standard 150 PSIG.
3. Provide Raised Face Flanges for eld installation on cooler nozzles and eld piping:
a. 150 PSIG, welded Flanges.
b. 300 PSIG, welded Flanges.
V. Service Isolation valves: Service suction and discharge (ball type) isolation valves are
added to unit per system. This option also includes a system high pressure relief valve
in compliance with ASHRAE 15. (Factory-mounted.)
Guide Specifications (Cont'd)