FORM 150.67-EG1 (219)
JOHNSON CONTROLS
37
MODEL: YCAL0052EE
AIR TEMPERATURE ON CONDENSER (°C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 50.0
KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP
5.0 140.8 30.6 4.1 135.2 33.9 3.6 129.0 37.8 3.1 122.2 42.1 2.7 114.7 47.0 2.3 106.5 52.3 1.9
6.0 145.2 30.8 4.2 139.5 34.1 3.7 133.2 38.0 3.2 126.1 42.3 2.7 118.5 47.2 2.3 110.2 52.5 2.0
7.0 149.7 31.0 4.3 143.9 34.3 3.8 137.4 38.1 3.3 130.2 42.5 2.8 122.3 47.4 2.4 113.8 52.8 2.0
8.0 154.3 31.2 4.4 148.3 34.5 3.9 141.7 38.3 3.4 134.3 42.7 2.9 126.3 47.6 2.5 117.6 53.0 2.1
9.0 158.9 31.5 4.5 152.9 34.7 4.0 146.0 38.5 3.4 138.5 42.9 3.0 130.3 47.8 2.5 121.4 53.2 2.1
10.0 163.7 31.7 4.6 157.5 34.9 4.1 150.5 38.8 3.5 142.8 43.1 3.0 134.4 48.0 2.6 125.2 53.5 2.2
11.0 168.5 32.0 4.7 162.2 35.2 4.2 155.0 39.0 3.6 147.1 43.3 3.1 138.5 48.3 2.7 129.2 53.7 2.2
MODEL: YCAL0056EE
AIR TEMPERATURE ON CONDENSER (°C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 50.0
KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP
5.0 172.6 39.1 4.0 165.5 43.4 3.5 157.6 48.3 3.0 148.9 53.8 2.6 139.5 59.9 2.2 69.6 29.7 2.1
6.0 177.9 39.4 4.1 170.6 43.7 3.6 162.5 48.6 3.1 153.6 54.1 2.7 144.0 60.2 2.3 72.0 29.8 2.1
7.0 183.3 39.7 4.2 175.9 44.0 3.7 167.6 48.9 3.2 158.5 54.5 2.7 148.6 60.6 2.3 74.5 29.9 2.2
8.0 188.8 40.0 4.3 181.2 44.3 3.8 172.7 49.2 3.3 163.4 54.8 2.8 153.2 60.9 2.4 77.0 30.0 2.3
9.0 194.5 40.3 4.4 186.6 44.6 3.9 177.9 49.5 3.3 168.4 55.1 2.9 158.0 61.3 2.4 79.6 30.1 2.3
10.0 200.2 40.6 4.5 192.2 44.9 3.9 183.3 49.9 3.4 173.5 55.4 2.9 162.8 61.7 2.5 82.3 30.2 2.4
11.0 206.0 41.0 4.6 197.8 45.3 4.0 188.7 50.2 3.5 178.6 55.8 3.0 167.8 62.0 2.6 85.0 30.3 2.5
MODEL: YCAL0066EE
AIR TEMPERATURE ON CONDENSER (°C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 50.0
KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP
5.0 204.4 47.8 4.0 195.3 52.7 3.5 185.6 58.4 3.0 175.2 64.8 2.6 164.2 72.2 2.2 113.8 54.4 2.0
6.0 210.8 48.2 4.1 201.5 53.1 3.5 191.5 58.8 3.1 181.0 65.3 2.6 169.7 72.7 2.2 117.8 54.6 2.0
7.0 217.3 48.6 4.1 207.8 53.5 3.6 197.6 59.2 3.1 186.8 65.7 2.7 175.3 73.1 2.3 121.8 54.9 2.1
8.0 224.0 49.1 4.2 214.2 54.0 3.7 203.7 59.6 3.2 192.6 66.2 2.8 180.9 73.6 2.3 126.0 55.1 2.1
9.0 230.7 49.5 4.3 220.7 54.4 3.8 210.0 60.1 3.3 198.6 66.6 2.8 186.6 74.1 2.4 130.2 55.4 2.2
10.0 237.6 50.0 4.4 227.4 54.9 3.9 216.4 60.6 3.4 204.8 67.1 2.9 192.4 74.6 2.5 134.5 55.7 2.3
11.0 244.6 50.4 4.5 234.2 55.3 4.0 222.9 61.0 3.4 211.0 67.6 3.0 198.4 75.1 2.5 138.9 56.0 2.3
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with the latest version of ARI Standard 550/590
6. The shaded points are certied in accordance with the latest version of ARI Standard 550/590
Ratings (Cont'd)
R-410A (50HZ) SI