EasyManua.ls Logo

York YCAL0043 - Supply Voltage; PREPARATION - POWER ON; Switch Settings; Compressor Heaters

York YCAL0043
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
148
FORM 150.67-NM2
ISSUE DATE: 01/31/2019
SECTION 7 – UNIT CONTROL CENTER
U N I T T R I P V O L T S
= X . X V O L T S
Depending on the option, the trip voltage for a
specific system or unit high current trip can be
programmed. It also calibrates the current read-
out under the OPER DATA key. The approximate
programmed value is calculated using the following
formulas:
System Trip Volts
For individual system high current trip programming
on chillers:
Add the sum of the compressor and fan RLAs in
the system
Multiply the sum by 1.25
Divide by 225A
The resulting voltage is the value that should be
programmed
For example, if fan and compressor RLAs total 100A:
5V x 100A
x 1.25 =
625VA
= 2.8V
225A 225A
The programmed value will be 2.8V. A similar calcula-
tion and programming will be necessary for the other
system in a 2-system chiller.
Unit Trip Volts
For total chiller high current trip programming on
460VAC chillers:
Add the sum of all the the compressor and fan
RLAs in the chiller.
Multiply the sum by 1.25
Divide by 225A
The resulting voltage is the value that should be
programmed.
For example, if fan and compressor RLAs total 180A:
5V x 180A
x 1.25 =
1125VA
= 5.0V
225A 225A
The programmed value will be 5.0V.
F A N D I F F E R E N T I A L O F F
P R E S S U R E = X X X P S I G
The Fan Differential Off Pressure is the programmed
differential pressure value that is used to stage the con-
denser fans off, in relation to discharge pressure. Refer
to Condenser Fan Control in SECTION 8 – UNIT OP-
ERATION and see Tables 22, 23, 24 and 25 starting on
page 163.
T O T A L N U M B E R O F
C O M P R E S S O R S = 6
The TOTAL NUMBER OF COMPRESSORS is the
total quantity of compressors in the chiller, and deter-
mines the stages of cooling available. Note in Table 16
on page 149, the chiller may have single or dual sys-
tems. Single system units can have 2 or 3 compressors,
while dual system units may have 4 or 6 compressors.
This MUST be programmed correctly to
assure proper chiller operation.
A single system chiller MUST have a
jumper between terminals J9-7 and +24V
on the I/O board. This connection can
be made between terminals 13 and 17 on
terminal block CTB1. If the jumper is not
installed, the unit will act as a 2-system
chiller. The jumper is only checked by the
micro at unit power-up. If the jumper is
removed, power must be removed and re-
applied to register the change in memory.
This MUST be programmed correctly to
assure proper chiller operation.
N U M B E R O F F A N S
P E R S Y S T E M = X
The Number of Fans Per System must be programmed
as needed to match the number of fans on each system.
S Y S X T R I P V O L T S
= X . X V O L T S

Table of Contents

Other manuals for York YCAL0043

Related product manuals