ELECTRICAL DATA (CONT'D)
COMPRESSOR DATA
MAXIMUM kW AND AMPERAGE VALUES FOR DXST COMPRESSORS
COMPRESSOR MODEL AND VOLTAGE CODE
DXS45LA – MOTOR CODE A DXS36LA – MOTOR CODE A DXS24LA – MOTOR CODE (TBD)
(B5N, B5E, B6N, B6E) (A5N, A5E, A6N, A6E) (C5N, C5E, C6N, C6E)
VOLTAGE CODE- 50 50 50
MAX kW 113 113 80
MAX AMPS 193 193 135
CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMERS)
NO. OF
CONTROL MCA MAX DUAL NON-FUSED
COMPRESSORS
POWER (MAX LOAD ELEMENT DISCONNECT
SUPPLY CURRENT) FUSE SIZE SWITCH SIZE
2 115V-1Ø 20A 20A 30A
CONTROL POWER SUPPLY (UNITS WITH STANDARD CONTROL CIRCUIT TRANSFORMER)
NO. OF
CONTROL MCA RECOMMENDED NON-FUSED
COMPRESSORS
POWER (MAX LOAD DUAL
ELEMENT DISCONNECT
SUPPLY CURRENT) FUSE SIZE SWITCH SIZE
2 400V - 50 HZ 6.3A 15A