TABLE 1 – COMPRESSOR DATA
MAXIMUM kW AND AMPERAGE VALUES FOR DXST COMPRESSORS
COMPRESSOR MODEL AND VOLTAGE CODE
DXS45LA – MOTOR CODE A DXS36LA – MOTOR CODE A DXS24LA – MOTOR CODE (TBD)
(B5N, B5E, B6N, B6E) (A5N, A5E, A6N, A6E) (C5N, C5E, C6N, C6E)
VOLTAGE CODE- -17 -28 -40 -46 -50 -58 -17 -28 -40 -46 -50 -58 -17 -28 -40 -46 -50 -56
MAX kW 150 150 150 150 113 150 150 150 150 150 113 150 105 105 105 105 80 105
MAX AMPS 492 428 259 214 193 171 492 428 259 214 193 171 338 294 178 147 135 118
CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMER)
NO. OF COMPRESSORS
CONTROL POWER
SUPPLY
MCA (MAX LOAD
CURRENT)
MAX DUAL ELEMENT
FUSE SIZE
NON-FUSED
DISCONNECT
SWITCH SIZE
3 or 4 (Non-CE 50/60Hz) 115V-1Ø 30A 30A 30A
CONTROL POWER SUPPLY (UNITS WITH STANDARD CONTROL CIRCUIT TRANSFORMER)
NO. OF COMPRESSORS
CONTROL POWER
SUPPLY
MCA (MAX LOAD
CURRENT)
RECOMMENDED
DUAL ELEMENT FUSE
SIZE
NON-FUSED
DISCONNECT
SWITCH SIZE
3 or 4
380V - 60 HZ 460V -
60 HZ 575V - 60 HZ
9.9A 8.2A 6.5A 30A 15A 15A — — —