FORM 150.40-NM20
7
YORK INTERNATIONAL
CONTROL SUPPLY WITH LOAD RATINGS
TRANSFORMER SYSTEM NO. 1 SYSTEM NO. 2
MAX. DUAL NON-FUSED
COMPRESSOR CONDENSER COMPRESSOR CONDENSER
MIN. ELEM. DISC.
LOAD FAN LOADS LOAD FAN LOADS
CIR. FUSE SWITCH SZ.
AMP. PW- TRIP PW- TRIP
AVAVRLA
LRA AMPS
3
NO HP KW FLA RLA
LRA AMPS
3
NO HP KW FLA
15 15 250 30 240 380 1311 501.9 4 3 2.2 11.4
15 15 250 30 240 332 1212 445.6 4 3 2.2 11.4
8 8 600 30 480 199 733 264.4 4 3 2.2 5.8
8 8 600 30 480 166 606 219.5 4 3 2.2 5.7
8 8 600 30 480 204 760 272.4 4 3 2.2 6.2
8 8 600 30 480 234 897 314.6 4 3 2.2 6.6
15 15 250 30 240 198 665 262.7 3 3 2.2 11.4 267 950 363.0 4 3 2.2 11.4
15 15 250 30 240 170 602 224.9 3 3 2.2 11.4 232 826 314.6 4 3 2.2 11.4
8 8 600 30 480 104 364 139.0 3 3 2.2 5.8 140 500 192.5 4 3 2.2 5.8
8 8 600 30 480 86 301 116.2 3 3 2.2 5.7 116 413 159.4 4 3 2.2 5.7
8 8 600 30 480 104 400 139.0 3 3 2.2 6.2 145 590 197.1 4 3 2.2 6.2
8 8 600 30 480 114 450 149.2 3 3 2.2 6.6 159 700 216.8 4 3 2.2 6.6
15 15 250 30 240 272 950 363.0 4 3 2.2 11.4 272 950 363.0 4 3 2.2 11.4
15 15 250 30 240 238 826 314.6 4 3 2.2 11.4 238 826 314.6 4 3 2.2 11.4
8 8 600 30 480 144 471 192.5 4 3 2.2 5.8 144 471 192.5 4 3 2.2 5.8
8 8 600 30 480 119 413 159.4 4 3 2.2 5.7 119 413 159.4 4 3 2.2 5.7
8 8 600 30 480 148 590 197.1 4 3 2.2 6.2 148 590 197.1 4 3 2.2 6.2
8 8 600 30 480 163 700 216.8 4 3 2.2 6.6 163 700 216.8 4 3 2.2 6.6
15 15 250 30 240 283 950 376.5 4 3 2.2 11.4 377 1311 501.9 4 3 2.2 11.4
15 15 250 30 240 246 826 325.9 4 3 2.2 11.4 328 1212 445.6 4 3 2.2 11.4
8 8 600 30 480 149 471 197.1 4 3 2.2 5.8 199 733 264.4 4 3 2.2 5.8
8 8 600 30 480 123 413 162.6 4 3 2.2 5.7 164 606 219.5 4 3 2.2 5.7
8 8 600 30 480 152 590 201.8 4 3 2.2 6.2 202 760 272.4 4 3 2.2 6.2
8 8 600 30 480 167 700 224.9 4 3 2.2 6.6 232 897 314.6 4 3 2.2 6.6
15 15 250 30 240 380 1311 501.9 4 3 2.2 11.4 380 1311 501.9 4 3 2.2 11.4
15 15 250 30 240 332 1212 445.6 4 3 2.2 11.4 332 1212 445.6 4 3 2.2 11.4
8 8 600 30 480 199 733 264.4 4 3 2.2 5.8 199 733 264.4 4 3 2.2 5.8
8 8 600 30 480 166 606 219.5 4 3 2.2 5.7 166 606 219.5 4 3 2.2 5.7
8 8 600 30 480 204 760 272.4 4 3 2.2 6.2 204 760 272.4 4 3 2.2 6.2
8 8 600 30 480 234 897 314.6 4 3 2.2 6.6 234 897 314.6 4 3 2.2 6.6
ELECTRICAL DATA
The above recommendations are based on the National Electrical Code. Field wiring must also comply with local codes.
3
Current Overload Setting – Protects motor by stopping unit if compressor motor current exceeds values shown.
LEGEND
A = Amps
AMP. = Ampacity
HZ = Hertz
HP = Horsepower
PH = Phase
V = Volts
RLA = Running Load Amps
FLA = Full Load Amps
PW = Part Wind