JOHNSON CONTROLS
FORM 201.23-EG2 (713)
11
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°C)
COOLER
3
FLOW
(L/S)
AIR ON CONDENSER (°C)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
50 HZ
0920(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0930(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
1000(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
1050(E/V) 4.4 15.6 11.4 50.5 -17.8 51.7
1070(S/P) 4.4 15.6 15.8 75.7 -17.8 51.7
1120(E/V) 4.4 15.6 15.8 75.7 -17.8 51.7
1180(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
1220(E/V) 4.4 15.6 18.9 75.7 -17.8 51.7
1340(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
1380(E/V) 4.4 15.6 18.9 75.7 -17.8 51.7
1500(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
1649(P) 4.4 15.6 25.2 88.2 -17.8 51.7
TEMPERATURE AND FLOWS
(SI Units)
NOTES:
1. Forleavingbrinetemperaturebelow4.4°C(40°F),contactyournearestJohnsonControlsofceforapplicationrequirements.
2. Forleavingwatertemperaturehigherthan15.6°C(60°F),contactthenearestJohnsonControlsofceforapplicationguidelines.
3. Theevaporatorisprotectedagainstfreezingto-28.8°C(-20°F)withanelectricheaterasstandard.