TEMPERATURE AND FLOWS
(SI Units)
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°C)
COOLER
3
FLOW
(L/S)
AIR ON CONDENSER (°C)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
60 HZ
0157(S/P) 4.4 15.6 8.8 42.6 -17.8 51.7
0157(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0177(S/P) 4.4 15.6 10.1 47.3 -17.8 51.7
0177(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0187(S/P) 4.4 15.6 10.1 47.3 -17.8 51.7
0187(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0197(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0207(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0207(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0227(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0227(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0247(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0247(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0267(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0267(E/V) 4.4 15.6 11.4 50.5 -17.8 51.7
0287(S/P) 4.4 15.6 15.8 75.7 -17.8 51.7
0287(E/V) 4.4 15.6
15.8 75.7 -17.8 51.7
0307(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
0327(E/V) 4.4 15.6 18.9 75.7 -17.8 51.7
0357(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
0357(E/V) 4.4 15.6 18.9 75.7 -17.8 51.7
0397(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
0457(P) 4.4 15.6 25.2 88.2 -17.8 51.7
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls ofce for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest Johnson Controls ofce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.