JOHNSON CONTROLS
47
SECTION 5 – TECHNICAL DATA
Form 150.63-NM9
Issue date: 5/20/2021
5
CHILLER
MODEL
YCUL
VOLT HZ
MINIMUM
CIRCUIT
AMPS
MCA
MIN N/F
DISC SW
MDSW
MIN
DUAL
ELEM
FUSE
MAX
DUAL
ELEM
FUSE
MAX CB
SYSTEM # 1 SYSTEM # 2
COMPR 1 COMPR 2 FAN COMPR 1 COMPR 2 FAN
RLA LRA RLA LRA QTY FLA LRA RLA LRA RLA LRA QTY FLA LRA
0065
200 60 268 400 300 300 55.8 425 55.8 425 2 7.6 44 55.8 425 55.8 425 2 7.6 44
230 60 267 400 300 300 55.8 425 55.8 425 2 7.4 19.1 55.8 425 55.8 425 2 7.4 19.1
380 60 171 200 200 200 36 239 36 239 2 4.5 23.1 36 239 36 239 2 4.5 23.1
400 50 114 150 125 125 23.7 198 23.7 198 2 3.4 17.5 23.7 198 23.7 198 2 3.4 17.5
460 60 130 150 150 150 26.9 187 26.9 187 2 4 19 26.9 187 26.9 187 2 4 19
575 60 112 150 125 125 23.7 148 23.7 148 2 2.9 15.3 23.7 148 23.7 148 2 2.9 15.3
0072
200 60 324 400 350 400 76.9 505 76.9 505 2 7.6 30.9 59.9 425 59.9 425 2 7.6 30.9
230 60 301 400 350 350 71.2 505 71.2 505 2 7.4 37 55.5 425 55.5 425 2 7.4 37
380 60 175 200 200 200 41.1 280 41.1 280 2 4.5 22.3 32 239 32 239 2 4.5 22.3
400 50 146 200 175 175 33.9 225 33.9 225 2 4 19 26.4 198 26.4 198 2 4 19
460 60 143 200 175 175 33.9 225 33.9 225 2 3.4 17.2 26.4 187 26.4 187 2 3.4 17.2
575 60 115 150 125 125 27.1 180 27.1 180 2 2.9 14.6 21.1 148 21.1 148 2 2.9 14.6
Electrical data
YCUL0020 - YCUL0072