EasyManua.ls Logo

York YCUL0065EE - FIGURE 36 - Two Inch Deflection Seismic Isolator Cross-Reference; Two Inch Deflection Seismic Isolator Cross-Reference

York YCUL0065EE
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
98
Form 150.63-NM9
Issue date: 5/20/2021
SECTION 5 TECHNICAL DATA
Two inch deflection seismic isolator cross-reference
LD13761A
12"
5"
2-3/4"
12-1/4"
8-3/8"
OPER.
HEIGHT
14"
5/8"
3/8"
Ø3/4"
TYP.(4)
3-1/2"
5/8-11UNC
TYP. (4)
2-3/4"
3/4"
7/8"
1-1/8"
3/8" GAP
5"
1/2" LIMIT
STOP &
NUT
NOTES:
1. ALL DIMENSIONS ARE IN INCHES, INTERPRET PER ANSI Y14.
2. STANDARD FINISH: HOUSING-POWDER COATED (COLOR:BLACK), SPRING-POWDER COATED (COLOR: SEE T
HARDWARE ZINC-ELECTROPLATE.
3. EQUIPMENT MUST BE BOLTED OR WELDED TO THE TOP PLATE TO MEET ALLOWABLE SEISMIC RATINGS.
4. ALL SPRINGS ARE DESIGNED FOR 50% OVERLOAD CAPACITY WITH EXCEPTION OF THE 2D-3280N & 2D-2870
5. REFER TO NEXT PAGE FOR INSTALLATION INSTRUCTIONS.
6. CONSULT FACTORY FOR CONCRETE INSTALLATION.
MODEL Y2RSI-2D SEISMICALLY RESTRAINED VIBRATION ISOLATOR FOR 2 IN. DEFLECTION
SEISMIC MOUNT
SIZE
RATED
LOAD (LB)
RATED
DEFLECTION
(IN.)
SPRING
RATE (LB/
IN.)
SOLID
LOAD
(LB)
COLOR CODE
ALLOWABLE
G RATING
HORIZONTAL
Y2RSI-2D-150
150 2.4 62 234 WHITE 34.7
Y2RSI-2D-320
320 2.3 140 490 YELLOW 16.3
Y2RSI-2D-460
460 2.3 200 688 GREEN 11.3
Y2RSI-2D-710
710 2.2 330 1072 DK BROWN 7.3
Y2RSI-2D-870
870 1.9 460 1312 RED 6
Y2RSI-2D-1200N
1200 1.9 638 1818 RED/BLACK 4.3
Y2RSI-2D-1450
1450 1.8 900 2450 TAN 3.6
Y2RSI-2D-1690
1690 1.7 1140 2892 PINK 3.1
Y2RSI-2D-2000N
2000 1.7 1318 3342 PINK/BLACK 2.6
Y2RSI-2D-2640N
2640 1.5 1854 4283 PINK/GRAY 2
Y2RSI-2D-2870N
3080 1.5 2004 4629 PINK/GRAY/ORANGE 1.7
Y2RSI-2D-3280N
3740 1.8 2134 4930 PINK/GRAY/DK BROWN 1.4
Figure 36 - Two Inch Deflection Seismic Isolator Cross-Reference
NOTES:
1. All dimensions are in inches, interpret beforeANSI Y14.
2. Standard nish: housing-powder coated (color, black), spring-powder coated (color, see table) hardware - zinc-electroplate.
3. Equipment must be bolted or welded to the top plate to meet allowable seismic ratings.
4. All springs are designed for 50% overload capacity with exception of the 2D-3280N and 2D-2870.
5. See next page for installation instructions.
6. Consult factory for concrete installation.

Table of Contents