FORM 150.26-EG1 (116)
JOHNSON CONTROLS
29
o = Unit kW Cooling Capacity Output
2. KWi = Compressor kW Input
3. KW = Condenser Heat Rejection
4. COP
= Coefficient of Performance
= Leaving Chilled Water Temperature
6. Ratings based on 0.047 l/s cooler water per kW.
MODEL: YCWL0127HE IPLV= 24.8
ENTERING CONDENSER WATER TEMPERATURE (°F)
LCWT
(°F)
75.0 85.0 95.0
TONS KW MBH EER TONS KW MBH EER TONS KW MBH EER
40.0 127.0 78.7 1792.0 19.4 119.5 91.7 1747.0 15.6 112.0 106.7 1708.0 12.6
42.0
131.8 78.3
1848.0 20.2 124.0 91.3 1800.0 16.3 116.2 106.2
1757.0
13.1
44.0 136.7 77.9 1906.0 21.1 128.7 90.8 1854.0 17.0 120.6 105.7 1808.0 13.7
46.0 141.8 77.5 1966.0 21.9 133.5 90.4 1910.0 17.7 125.1 105.2 1860.0 14.3
48.0
147.0 77.2
2027.0 22.9 138.4 89.9 1968.0 18.5 129.8 104.6
1914.0
14.9
50.0
152.4 76.8
2091.0 23.8 143.5 89.5 2027.0 19.2 134.6 104.2
1970.0
15.5
MODEL: YCWL0157HE IPLV= 24.3
ENTERING CONDENSER WATER TEMPERATURE (°F)
LCWT
(°F)
75.0 85.0 95.0
TONS KW MBH EER TONS KW MBH EER TONS KW MBH EER
40.0 146.9 90.5 2071.0 19.5 138.5 104.2 2017.0 15.9 129.8 120.2 1968.0 13.0
42.0 152.2 90.3 2135.0 20.2 143.6 103.9 2078.0 16.6 134.7 119.7 2025.0 13.5
44.0 157.8 90.1 2200.0 21.0 148.9 103.6 2140.0 17.2 139.8 119.3 2084.0 14.1
46.0 163.4 89.9 2267.0 21.8 154.3 103.3 2204.0 17.9 144.9 118.9 2145.0 14.6
48.0 169.2 89.7 2336.0 22.6 159.8 103.0 2269.0 18.6 150.2 118.5 2206.0 15.2
50.0
175.1 89.5
2406.0 23.5 165.5 102.7 2336.0 19.3 155.6 118.1
2270.0 15.8
Ratings - High Efficiency (Cont'd)