5855836-YTG-B-1121
58 Johnson Controls Ducted Systems
PERFORMANCE DATA - 3 TON
YPLC120C20MP13C CF/CM30C 0.96 1.06 0.90
YPLC120C20MP13C XAFC30C 1.01 1.08 0.94
YPLC120C20MP13C XAHC30C 1.03 1.07 0.96
FURNACE MULTIPLIERS - 2.5 TON (Continued)
Furnaces Coil MBH COP KW
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
AT COMPRESSOR
Outdoor Ambient Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F 125 °F
T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
YEE36B21S
35 107 34.2 1.67 32.5 1.93 30.5 2.17 28.5 2.45 26.2 2.73 23.8 3.06 21.4 3.44
40 119 38.0 1.72 36.0 1.96 33.8 2.20 31.5 2.47 29.0 2.75 26.4 3.08 23.8 3.46
45 130 41.8 1.76 39.5 2.00 37.1 2.23 34.6 2.50 31.9 2.78 29.1 3.10 26.2 3.48
50 143 45.5 1.81 43.1 2.04 40.4 2.26 37.7 2.53 34.7 2.80 31.7 3.12 28.6 3.50
55 156 49.3 1.86 46.6 2.08 43.7 2.29 40.8 2.56 37.6 2.83 34.3 3.14 31.0 3.51
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15ºF subcooling and 15ºF superheat at the Outdoor /Unit base valves.
a. Increase capacity by 1% for each 2ºF increase in subcooling.
b. Decrease capacity by 1% for each 2ºF decrease in subcooling.
3. Maximum recommended condensing temperature is 140ºF.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. YEE36B21S
AIR TEMPERATURE
ENTERING
OUTDOOR UNIT (°F)
IDCFM 900 1200 1500
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
55
T.C. 31.8 34.6 34.5 37.2 39.6 34.0 36.0 35.7 38.0 40.2 36.3 37.4 36.9 38.9 40.8
S.C. 31.8 28.5 24.5 24.4 19.1 34.0 31.7 26.8 26.1 19.8 36.3 35.0 29.1 27.8 20.5
KW 1.94 1.93 1.93 1.92 1.92 2.03 2.03 2.03 2.02 2.04 2.12 2.13 2.13 2.13 2.16
65
T.C. 30.8 33.4 33.4 36.4 39.1 33.2 34.8 34.6 37.4 39.9 35.5 36.2 35.8 38.4 40.7
S.C. 30.8 28.3 23.9 24.0 18.8 33.2 31.9 26.4 26.2 19.9 35.5 35.6 28.9 28.4 21.0
KW 2.13 2.12 2.12 2.12 2.12 2.23 2.23 2.23 2.22 2.23 2.33 2.33 2.33 2.33 2.35
75
T.C. 29.8 32.2 32.2 35.3 38.3 32.2 33.5 33.4 36.4 39.3 34.5 34.9 34.6 37.6 40.2
S.C. 29.8 27.9 23.3 23.5 18.4 32.2 31.4 25.9 26.1 19.8 34.5 34.9 28.5 28.7 21.1
KW 2.35 2.35 2.35 2.35 2.35 2.45 2.45 2.45 2.46 2.46 2.56 2.56 2.56 2.56 2.57
85
T.C. 28.7 30.8 30.9 34.0 37.2 31.1 32.1 32.0 35.2 38.2 33.4 33.5 33.1 36.4 39.3
S.C. 28.7 27.4 22.7 23.0 18.0 31.1 30.4 25.4 25.8 19.5 33.4 33.5 28.1 28.7 21.0
KW 2.61 2.60 2.61 2.61 2.61 2.72 2.71 2.72 2.72 2.72 2.83 2.82 2.82 2.83 2.83
95
T.C. 27.6 29.3 29.3 32.5 35.8 29.8 30.6 30.4 33.7 36.9 32.1 32.0 31.5 34.9 37.9
S.C. 27.6 26.6 22.0 22.4 17.6 29.8 29.3 24.7 25.3 19.1 32.1 32.0 27.4 28.3 20.6
KW 2.90 2.90 2.90 2.91 2.91 3.01 3.01 3.01 3.02 3.02 3.12 3.12 3.12 3.13 3.13
105
T.C. 26.3 27.7 27.7 30.8 34.1 28.4 29.0 28.7 31.9 35.1 30.6 30.4 29.7 33.0 36.1
S.C. 26.3 25.7 21.3 21.7 17.0 28.4 28.0 24.0 24.6 18.5 30.6 30.4 26.6 27.5 19.9
KW 3.23 3.23 3.23 3.24 3.24 3.34 3.34 3.34 3.34 3.35 3.45 3.45 3.44 3.45 3.46
115
T.C. 25.0 26.0 25.8 28.8 32.0 26.9 27.4 26.7 29.8 32.9 28.9 28.7 27.6 30.7 33.8
S.C. 25.0 24.5 20.5 20.8 16.3 26.9 26.6 23.1 23.6 17.6 28.9 28.7 25.6 26.3 18.9
KW 3.59 3.59 3.59 3.59 3.60 3.70 3.70 3.69 3.70 3.71 3.81 3.81 3.80 3.81 3.82
125
T.C. 23.6 24.1 23.8 26.7 29.7 25.3 25.6 24.6 27.4 30.4 27.0 27.0 25.4 28.1 31.1
S.C. 23.6 23.2 19.6 19.8 15.5 25.3 25.1 22.0 22.3 16.6 27.0 27.0 24.4 24.7 17.6
KW 3.99 3.99 3.98 3.99 3.99 4.10 4.10 4.09 4.10 4.11 4.21 4.21 4.19 4.21 4.23
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR AND INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.