EasyManua.ls Logo

York YHE36B22S - PERFORMANCE DATA - 1.5 TON

York YHE36B22S
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5523949-YTG-J-0620
106 Johnson Controls Ducted Systems
PERFORMANCE DATA - 1.5 TON
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F 125 °F
T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
YHE18B21S
35 107 16.2 0.94 15.4 1.06 14.5 1.20 13.6 1.35 12.6 1.53 11.6 1.73 10.6 1.96
40 119 17.9 0.92 17.0 1.05 16.0 1.81 15.0 1.33 14.0 1.51 12.9 1.72 11.8 1.95
45 130 19.7 0.90 18.7 1.03 17.7 1.17 16.6 1.32 15.5 1.49 14.3 1.70 13.1 1.93
50 143 21.7 0.88 20.6 1.01 19.5 1.15 18.3 1.30 17.1 1.49 15.8 1.68 14.5 1.90
55 156 23.8 0.86 22.6 0.99 21.3 1.13 20.1 1.28 18.8 1.46 17.4 1.66 16.0 1.88
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15ºF subcooling and 15ºF superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2ºF increase in subcooling.
b. Decrease capacity by 1% for each 2ºF decrease in subcooling.
3. Maximum recommended condensing temperature is 140ºF.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. YHE18B21S
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
IDCFM 450 600 750
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 17.0 18.5 18.7 20.4 22.2 18.4 19.4 19.3 21.1 22.6 19.7 20.3 19.9 21.8 23.1
S.C. 16.7 14.7 12.7 12.5 10.2 18.1 16.6 14.3 14.1 11.1 19.6 18.6 15.9 15.8 12.0
KW 1.10 1.10 1.10 1.10 1.09 1.15 1.16 1.16 1.15 1.14 1.20 1.21 1.21 1.21 1.20
75
T.C. 16.4 17.6 17.9 19.6 21.5 17.7 18.4 18.5 20.3 22.0 19.0 19.1 19.0 21.0 22.4
S.C. 16.1 14.4 12.3 12.2 9.9 17.5 16.7 13.9 13.9 10.8 18.8 19.0 15.5 15.6 11.7
KW 1.21 1.21 1.21 1.21 1.20 1.26 1.26 1.26 1.26 1.25 1.31 1.32 1.32 1.31 1.30
85
T.C. 15.8 17.1 17.1 18.9 20.6 17.0 17.6 17.6 19.4 21.0 18.2 18.1 18.1 20.0 21.4
S.C. 15.5 13.9 12.0 12.0 9.6 16.8 16.0 13.6 13.6 10.5 18.1 18.1 15.2 15.2 11.5
KW 1.35 1.35 1.35 1.35 1.34 1.40 1.41 1.40 1.40 1.39 1.45 1.46 1.46 1.45 1.45
95
T.C. 15.2 16.7 16.2 18.1 19.6 16.3 16.9 16.7 18.5 20.0 17.4 17.1 17.2 18.9 20.3
S.C. 14.9 13.3 11.7 11.7 9.2 16.1 15.2 13.3 13.3 10.2 17.3 17.1 14.9 14.8 11.2
KW 1.49 1.49 1.49 1.49 1.48 1.54 1.55 1.55 1.54 1.53 1.59 1.60 1.60 1.59 1.59
105
T.C. 14.4 15.4 15.1 17.0 18.4 15.4 15.8 15.6 17.3 18.7 16.4 16.1 16.0 17.7 18.9
S.C. 14.2 12.9 11.2 11.2 8.8 15.2 14.5 12.8 12.8 9.7 16.3 16.1 14.3 14.3 10.7
KW 1.71 1.69 1.70 1.69 1.68 1.75 1.75 1.75 1.74 1.73 1.80 1.81 1.81 1.79 1.79
115
T.C. 13.5 14.3 14.1 15.9 17.2 14.5 14.7 14.5 16.2 17.4 15.5 15.1 14.9 16.5 17.6
S.C. 13.4 12.6 10.7 10.8 8.4 14.4 13.8 12.2 12.3 9.3 15.4 15.1 13.8 13.9 10.2
KW 1.92 1.89 1.89 1.88 1.87 1.96 1.95 1.95 1.93 1.93 2.00 2.00 2.01 1.99 1.98
125
T.C. 12.7 13.1 13.1 14.8 16.0 13.6 13.6 13.4 15.1 16.2 14.5 14.1 13.7 15.3 16.3
S.C. 12.7 12.2 10.2 10.3 8.0 13.6 13.2 11.7 11.9 8.9 14.4 14.1 13.2 13.4 9.7
KW 2.14 2.09 2.09 2.08 2.06 2.17 2.15 2.15 2.13 2.12 2.20 2.20 2.21 2.18 2.17
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.

Related product manuals