JOHNSON CONTROLS
146
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
SECTION 7 – UNIT CONTROLS
TABLE 18 - YORKTALK 2 COMMUNICATIONS DATA MAP (CONT’D)
ENG ASCII York Talk York Talk N2
ENG
PAGE PAGE Point Character Address
POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Position POINT LIST DESCRIPTION 12345678910 REF
P43 P41 D. Monitor
nvoYTS01p043 SNVT_switch (95)
115 BD 12 Sys 1 Hot Gas Bypass Valve S S S S S P43
P44 P42 D. Monitor
nvoYTS01p044 SNVT_switch (95)
116 BD 13 Sys 1 Compressor 2 Run S S S S S P44
P45 P43 D. Monitor
nvoYTS01p045 SNVT_switch (95)
117 BD 14 Sys 2 Compressor 2 Run S S S S S P45
P46 P44 D. Monitor
nvoYTS01p046 SNVT_switch (95)
118 BD 15 Sys 2 Liquid Line Solenoid Valve S S S S S P46
P47 P45 D. Monitor
nvoYTS01p047 SNVT_switch (95)
119 BD 16 Lead System (0 = Sys 1, 1 = Sys 2) S S S S S P47
P48 P46 D. Monitor
nvoYTS01p048 SNVT_switch (95)
120 BD 17 Sys 1 Compressor 3 Run S S S S S P48
P49 P47 D. Monitor
nvoYTS01p049 SNVT_switch (95)
121 BD 18 Sys 2 Compressor 3 Run S S S S S P49
P50 P48 D. Monitor
nvoYTS01p050 SNVT_switch (95)
122 BD 19 Chilled Liquid Type (0=Water, 1=Glycol) SSSSS P50
nvoYTS01p051 SNVT_switch (95)
123 BD 20 Ambient Control Mode (0=Std Amb, 1=Low Amb) S S S S N P51
P52 P50 D. Monitor
nvoYTS01p052 SNVT_switch (95)
124 BD 21 Local/Remote Control Mode (0=Local, 1=Remote) S S S S S P52
P53 P51 D. Monitor
nvoYTS01p053 SNVT_switch (95)
125 BD 22 Units (0=Imperial, 1=SI) S S S S S P53
P54 P52 D. Monitor
nvoYTS01p054 SNVT_switch (95)
126 BD 23 Lead/Lag Control Mode (0=Manual, 1=Auto) S S S S S P54
P55 P53 D. Monitor
nvoYTS01p055 SNVT_switch (95)
127 BD 24 Sys 2 Hot Gas Bypass Valve S S S S S P55
P56 P54 Code Monitor
nvoYTS01p056 SNVT_count_f (51)
128 ADI 1 *Sys 1 Operational Code S S S S S P56
P57 P55 Code Monitor
nvoYTS01p057 SNVT_count_f (51)
129 ADI 2 *Sys 1 Fault Code S S S S S P57
P58 P56 Code Monitor
nvoYTS01p058 SNVT_count_f (51)
130 ADI 3 *Sys 2 Operational Code S S S S S P58
P59 P57 Code Monitor
nvoYTS01p059 SNVT_count_f (51)
131 ADI 4 *Sys 2 Fault Code S S S S S P59
P60 P58 Code Monitor
nvoYTS01p060 SNVT_count_f (51)
132 ADI 5 SSSSS P60
nvoYTS01p061 SNVT_count_f (51)
133 ADI 6 Sys 1 Condenser Fan Stage S S S S S P61
P62 P60 Code Monitor
nvoYTS01p062 SNVT_count_f (51)
134 ADI 7 SSSSS P62
nvoYTS01p063 SNVT_count_f (51)
135 ADI 8 Sys 2 Condenser Fan Stage S S S S S P63
P64 P62 Code Monitor
nvoYTS01p064 SNVT_count_f (51)
136 ADI 9 P64
nvoYTS01p065 SNVT_count_f (51)
137 ADI 10 Unit Control Mode (0=Lv Wtr, 1=Ret Wtr, 2=Dis Air, 3=SP, 4=Cool, 5=Heat
SSSSS P65
nvoYTS01p066 SNVT_count_f (51)
138 - 141 ADF 30 Anti-Recycle Time (Programmed) S S S S S P66
P67 P65 A. Monitor
nvoYTS01p067 SNVT_count_f (51)
142 - 145 ADF 31 Leaving Chilled Liquid Temp Cutout SSSSS P67
nvoYTS01p068 SNVT_count_f (51)
146 - 149 ADF 32 Low Ambient Temperature Cutout S S S S S P68
P69 P67 A. Monitor
nvoYTS01p069 SNVT_count_f (51)
150 - 153 ADF 33 Low Suction Pressure Cutout (Heating HP Only) S S S S S P69
P70 P68 A. Monitor
nvoYTS01p070 SNVT_count_f (51)
154 - 157 ADF 34 Low Suction Pressure Cutout (Cooling HP only) S S S S S P70
P71 P69 A. Monitor
nvoYTS01p071 SNVT_count_f (51)
158 - 161 ADF 35 High Discharge Pressure Cutout S S S S S P71
P72 P70 A. Monitor
nvoYTS01p072 SNVT_count_f (51)
162 - 165 ADF 36 Remote Setpoint S S S S S P72
P73 P71 A. Monitor
nvoYTS01p073 SNVT_count_f (51)
166 - 169 ADF 37 Cooling Range S S S S S P73
P74 P72 A. Monitor
nvoYTS01p074 SNVT_count_f (51)
170 - 173 ADF 38 Remote Setpnt 2 ( SP Control), Remote Heatng Setpnt ( HP and YCWL H
OOOOO P74
nvoYTS01p075 SNVT_count_f (51)
174 - 177 ADF 39 Cool Range Setpoint 2 (SP Control), Heat Range (HP and YCWL HP only) O O O O O P75
P76 P74 A. Monitor
nvoYTS01p076 SNVT_count_f (51)
178 - 181 ADF 40 Sys 1 Discharge Temp (EEV only) OOOOO P76
nvoYTS01p077 SNVT_count_f (51)
182 - 185 ADF 41 Sys 1 Discharge Superheat (EEV only) OOOOO P77
nvoYTS01p078 SNVT_count_f (51)
186 - 189 ADF 42 Sys 2 Discharge Temp (EEV only) OOOOO P78
nvoYTS01p079 SNVT_count_f (51)
190 - 193 ADF 43 Sys 2 Discharge Superheat (EEV only) OOOOO P79
nvoYTS01p080 SNVT_switch (95)
194 BD 25 P80
nvoYTS01p081 SNVT_switch (95)
195 BD 26 P81
nvoYTS01p082 SNVT_switch (95)
196 BD 27 P82
nvoYTS01p083 SNVT_switch (95)
197 BD 28 P83
nvoYTS01p084 SNVT_switch (95)
198 BD 29 P84
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
LON Profile
Name
LON SNVT
Type
Revision: YCAL_YCWL_YCUL_YLAA_YLUA Small Tonnage Scroll (Rev K_03 ) Tab: YCAL-YCWL-YLAA-YLUA-YCRL 2550) Property of York International York, PA Page: 2