SECTION 2 – PRODUCT DESCRIPTION
The evaporator is equipped with a thermostat-con-
trolled heater. The heater provides freeze protection
for the evaporator down to -20°F (-29°C) ambient. The
evaporator is covered with 3/4” flexible, closed-cell,
foam insulation (K=0.25).
A 1/16” (1.6mm) mesh wye-strainer is provided as
standard for installation upstream of the heat exchang-
er to prevent clogging from water system debris.
Canadian Registration Number (CRN)
Application & Proof of Conformance
Since all YLAA brazed plate evaporators are catego-
rized as pressure “H” fittings per CSA-B51, a CRN
label or marking is not provided on the evaporator. Ac-
cording to the Canadian Standards Association’s Boil-
er, Pressure Vessel, and Pressure Piping Code B-51
(2009 version), a product registered as a category “H”
fitting does not require a label or marking displaying
the CRN.
TABLE 1 - CANADIAN REGISTRATION NUMBERS
CANADIAN PROVINCE CRN #
BC OH13953.51
AB OH13953.52
ON OH13953.5
PQ/MB/SK OH13953.56
NB OH13953.57
NS OH13953.58
PEI OH13953.59
NF OH13953.50
NU OH13953.5N
NWT OH13953.5T
YU OH13953.5Y
Condenser
Microchannel Condenser (MCHX)
MCHX Condensers are made of a single material to
avoid galvanic corrosion due to dissimilar metals.
MCHX and headers are brazed as one piece. Integral
sub cooling is included. The design working pressure
of the MCHX is 650 PSIG (45 bar). MCHX Condenser
is easily washable with clear water.
Fans
The condenser fans are composed of corrosion resis-
tant aluminum hub and glass-fiber reinforced poly-
propylene composite blades molded into a low noise
airfoil section. They are designed for maximum effi-
ciency and are statically and dynamically balanced for
vibration free operation. They are directly driven by
independent motors, and positioned for vertical air dis-
charge. The fan guards are constructed of heavy gauge,
rust resistant, coated steel. All blades are statically and
dynamically balanced for vibration free operation.
Motors
The fan motors are Totally Enclosed Air-Over, and are
current protected. They feature ball bearings that are
double sealed and permanently lubricated.
Control Center
All controls are contained in a NEMA 3R/12 cabinet
with hinged outer door and includes a Liquid Crystal
Display with Light Emitting Diode backlighting for
outdoor viewing:
Two display lines
Twenty characters per line
Display/Print Keys
Color coded 12-button non-tactile keypad with sec-
tions for display and print of typical information:
Chilled liquid temperatures
Ambient temperature
System pressures (each circuit)
Operating hours and starts (each compressor)
Print calls up to the liquid crystal display
Operating data for the systems
History of fault shutdown data for up to the last
six fault shutdown conditions.
An RS-232 port, in conjunction with this press-to-
print button, is provided to permit the capability
of hard copy print-outs via a separate printer (by
others).
Entry Keys
This section is used to enter setpoints or modify system
values.
Setpoints Keys
Updating can be performed to:
Chilled liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Low and high ambient cutouts