JOHNSON CONTROLS
119
SECTION 7 – UNIT CONTROLS
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
7
C O N T R O L M O D E
L E A V I N G L I Q U I D
Displays the type of chilled liquid control; Leaving or
Return.
L E A D / L A G C O N T R O L
X X X X X X X X
Displays the type of lead/lag control; Manual System
1, Manual System 2 or Automatic. This is only select-
able on 2-system chillers.
F A N C O N T R O L
D I S C H A R G E P R E S S U R E
Displays the type of fan control; Discharge Pressure or
Ambient and Discharge Pressure.
M A N U A L O V E R R I D E M O D E
X X X X X X X X X
Displays whether Manual Override was Enabled or
Disabled.
C U R R E N T F E E D B A C K
X X X X X X X X X X X X X X X X
Displays type of Current Feedback used.
S O F T S T A R T
X X X X X X X
Displays whether the optional European Soft Start was
installed and selected.
D I S C H A R G E P R E S S U R E
C U T O U T = X X X X P S I G
Displays the programmed Discharge Pressure Cutout.
S U C T I O N P R E S S U R E
C U T O U T = X X X X P S I G
Displays the programmed Suction Pressure Cutout.
L O W A M B I E N T T E M P
C U T O U T = X X X . X ° F
Displays the programmed Low Ambient Cutout.
History Displays
The HISTORY key gives the user access to many unit
and system operating parameters at the time of a unit
or system safety shutdown. When the HISTORY key is
pressed the following message is displayed.
D I S P L A Y S A F E T Y S H U T-
D O W N N O . 1 ( 1 T O 9 )
While this message is displayed, the ↑ (UP) arrow key
can be used to select any of the six history buffers. Buf-
fer number 1 is the most recent, and buffer number 6 is
the oldest safety shutdown that was saved.
After selecting the shutdown number, pressing the EN-
TER key displays the following message which shows
when the shutdown occurred.
S H U T D O W N O C C U R R E D
0 3 : 5 6 P M 2 9 J A N 0 2
The (UP) and (DOWN) arrow keys are used to
scroll forward and backward through the history buffer
to display the shutdown conditions stored at the instant
the fault occurred. The (DOWN) arrow key scrolls
through the displays in the order they appear below:
U N I T F A U L T :
L O W L I Q U I D T E M P
Displays the type of fault that occurred.
U N I T T Y P E
L I Q U I D C H I L L E R
Displays the type of chiller; Liquid, Condensing Unit
or Heat Pump.
C H I L L E D L I Q U I D
X X X X X
Displays the chilled liquid type; Water or Glycol.
A M B I E N T C O N T R O L
X X X X X X X X X X
Displays the type of Ambient Control; Standard or
Low Ambient.
L O C A L / R E M O T E M O D E
X X X X X X X X X
Displays Local or Remote control selection.