6
a) Consumption under nominal conditions.
b) Pressure under nominal conditions. See table on page 17 for other flows.
YLCC YLCC YLCC YLCC YLCC YLCC
42/42V 62/62V 82/82V 102/102V 122/122V 152/152V
Cooling capacity kW 40.2 64 71 96.1 116 137
Amount 2 2 2 2 2 2
Type Scroll Scroll Scroll Scroll Tandem-Scroll Tandem-Scroll
Nominal power (a) kW 8.3 (x2) 11.7 (x2) 13.7 (x2) 19.1 (x2) 27.6 (x2) 27.9 (x2)
Power supply V.ph.Hz 400.3.50
Comp. consump. in cool A 16.2 (x2) 21.3 (x2) 26.3 (x2) 34 (x2) 47.6 (x2) 50.9 (x2)
Start consumption A 130 135 175 215 135 175
Oil charge l 3.25 3.3 6.6 8 6.6 6.6
Oil type Polyolester ISO 32
Amount 2 2 2 2 2 2
Total nom. air flow m
3
/h 13 268 20 122 23 304 28 834 33 247 38 312
Fan size mm 12-12 15-15 15-15 18-18 18-18 18-18
Power (a) W 1 280 (x2) 2 407 (x2) 2 648 (x2) 3 549 (x2) 5 520 (x2) 6 360 (x2)
Fan consumption A 2.9 (x2) 5 (x2) 6.4 (x2) 6.9 (x2) 10.31 (x2) 11.5 (x2)
Start consumption A 17 35 60 60 75 75
Power supply V.ph.Hz 400.3.50
Motor r.p.m. 1 420 1 430 1 420 1 420 1 425 1 425
Available pressure (b) Pa 50 50 50 50 50 50
Amount 2 2 2 2 2 2
Pipes. depth x height 4 x 42 5 x 42 4 x 48 4 x 48 4 x 48 5 x 48
Fins per inch 14 14 16 16 16 16
Front surface m
2
1.02 (x2) 1.02 (x2) 1.56 (x2) 1.56 (x2) 1.77 (x2) 1.77 (x2)
Piping diameter 3/8"
Type Coaxial
bar 10 10 10 10 10 10
Nominal water flow l/h 6 760 11 020 12 285 16 424 19 404 22 948
Water connections. female G 2" 2" 2
1
/
2
" 2
1
/
2
" 3" 3"
Water filter 2" 2" 2
1
/
2
" 2
1
/
2
" 3" 3"
Refrigerant charge R-407C kg 7.3 (x2) 7.8 (x2) 11.2 (x2) 11.4 (x2) 12 (x2) 16 (x2)
Sound power level dB(A) 79 81 82 84 86 90
Sound power level at 5 m. dB(A) 57 59 60 62 64 70
Sound power level at 10 m. dB(A) 51 53 54 56 58 62
Height mm 1 770 1 770 1 994 1 994 1 994 1 994
Width mm 2 340 2 340 2 991 2 991 3 300 3 300
Depth mm 883 1 029 1 150 1 150 1 400 1 400
IP 44 44 44 44 44 44
Nett kg 695 816 962 1 133 1 389 1 522
Gross kg 712 834 981 1 153 1 411 1 544
Compressor
Max. operating pres-
sure on water side
Physical data and electrical characteristics
Cool only
Model
Centrifugal
fan
Outdoor
coil
Indoor
exchanger
D i m e n s i o n s
with packing
Approximate
weight