EasyManua.ls Logo

York YLCC-H - Limits of Use; Operating Limits and Electrical Characteristics

York YLCC-H
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
16 (x2) 130 1.5 3 (x2) 18 38 47 50 16
22 (x2) 135 3 4.6 (x2) 29 53 69 80 25
27 (x2) 175 4 6.4 (x2) 33 66 83 100 35
35 (x2) 215 4 7.4 (x2) 46 84 115 125 50
24 (x2) 135 5.5 10.3 (x2) 66 116 135 160 70
27 (x2) 175 5.5 11 (x2) 71 130 163 200 95
DB air intake temperature to coil
Water outlet temperature
Temperature differ-
ential between water
discharge and intake
YLCC 342 436 10 - 46 - 5* - 15 - 3 7
YLCC-H 342 436 10 -10 46 20 5* 30 15 50 3 7
Nominal at 400 V
Minimum °C
Máximo °CMinimum °CMáximo °C
Operating cycle
Operating cycle
* At water temperatures below the nominal limits, it is always necessary to use glycol-type antifreeze mixtures.
Voltage limits
Model
Minimum Máximo Cool Heat Cool Heat Cool Heat Cool Heat
Máximo
°C
Minimum
°C
Nominal
water
flow l/h
Model
YLCC-42 6 760 16.1 13 268 50
YLCC-62 11 020 43.5 20 122 50
YLCC-82 12 285 57 23 304 50
YLCC-102 16 424 94 28 834 50
YLCC-122 19 404 20.4 33 247 50
YLCC-152 22 948 45.6 38 312 50
Pressure
drop
Kpa
Nominal
air flow
m
2
/s
Available
pressure,
fan, Pa
Nominal water
flow l/h
Model
YLCC-H-42 7 107 6 829 16.4 13 268 50
YLCC-H-62 10 041 10 045 36.6 20 122 50
YLCC-H-82 12 211 13 629 56.6 23 304 50
YLCC-H-102 16 165 16 103 91 28 834 50
YLCC-H-122 17 977 18 889 17.5 37 403 50
YLCC-H-152 22 085 20 801 42.3 37 403 50
Pressure
drop
Kpa
Nominal
air flow
m
2
/s
Available
pressure,
fan, Pa
Frío Calor
Start
intensity
Model
Power
supply
Compressor
Operating
nom. intensity
kW
Nominal
amps
Outdoor fan motor
Total
nominal
intensity
(unit)
Automatic
switch
(K curve),
amps
Total nominal
Minimum
section of
cables mm
2
kW
400.3.50
400.3.50
400.3.50
400.3.50
400.3.50
400.3.50
Total max.
intensity
(unit)
YLCC-42 /
YLCC-H-42
YLCC-62 /
YLCC-H-62
YLCC-82 /
YLCC-H-82
YLCC-102 /
YLCC-H-102
YLCC-122 /
YLCC-H-122
YLCC-152
/YLCC-H-152
DB WB
Summer 35 24 12 7
Winter 7 6 40 45
Outdoor air
temperature °C
Water
intake tem-
perature °C
Water
discharge
temp. °C
Voltage
400 V
Limits of use
Limits of use, YLCC (cool only unit)
Water discharge temperature: +6° C to +15° C.
Brine discharge temperature: -5° C to +6° C.
Temperature difference in heat exchanger: 3 to 7° C.
Maximum air intake temperature: +46° C.
Minimum ambient temperature: +10° C (standard), -18° C
low ambient temperature kit (optional).
Limits of use, YLCC-H (heat pump unit)
Cool mode
Water discharge temperature: +6° C to +15° C.
Brine discharge temperature: -5° C to +6° C.
Temperature difference in heat exchanger: 3 to 7° C.
Maximum air intake temperature: +46° C.
Minimum ambient temperature: +10° C (standard), -18° C
low ambient temperature kit (optional).
Heat mode
Water discharge temperature: +30° C to +50° C.
Ambient temperature: -10° C to +20° C.
Temperature difference in heat exchanger: 3 to 7° C.
Minimum air intake temperature: C with maximum dis-
charge water temperature of 50° C.
Minimum air intake temperature: -5° C with maximum dis-
charge water temperature of 45° C.
Test conditions
Nominal flows, cool only
The cooling capacities on the corresponding tables are valid
for the following nominal flows:
Nominal flows, heat pump
The capacities on the corresponding tables are valid for the
following nominal flows:
Electrical characteristics

Related product manuals