In Timer Mode setting, press “FUNCTION” to switch
the modes between ONCE, DAILY and WEEKLY. Press
“CONFIRM” to save the value and auto switch to the next
setting. Press “TIMER” to cancel the operation and auto switch
to the next setting.
In WEEKLY timer setting, the weekdays are able to be
switched over by pressing “FUNCTION” key. Press “UP” to
“CONFIRM” the weekday timer activation and move on to the
next weekday. Press “DOWN” to cancel the activation of the
weekday and move on to the next.
The Schedule Timer setting will terminate if there’s no
operation for 5 seconds or “CANCEL” is pressed.
Parameter Setting
Press the “FUNCTION” key in daily display for 5 seconds to
enter System Parameter Setting screen. Repeat the operation to
enter Module Parameter Setting screen. The “LOCK” icon will
appear while the function is activated.
In System Parameter Setting, the parameters will be displayed
in hour display area (Area 1) in sequence by pressing
“FUNCTION” key.
In Module Parameter Setting, the modules can be switched over
by pressing “TIMER” key.
Press “UP” or “DOWN” to set the value and press
“CONFIRM” to save the value. The setting will terminate if
there’s no operation for 5 seconds or “CANCEL” is pressed.
Fault Diagnosis
Press “FUNCTION” and “CANCEL” keys for 5 seconds to
enter Fault Diagnosis. The “FAULT” icon will appear while the
function is activated.
The fault codes will be displayed in temperature display area
(Area 3) with time recorded. The serial number of the module
will be displayed as 10-bit of Area 4.
Press “UP” and “DOWN” for more fault information. A
maximum of 16 faults can be recorded.
The setting will terminate if there’s no operation for 5 seconds
or “CANCEL” is pressed.
Running Status
Press “FUNCTION” and “CONFIRM” keys for 5 seconds to
enter Running Status viewing screen. The digital and analog
inputs and outputs are displayed in sequence in hour display
area (Area 1) by pressing “UP” and “DOWN” keys.
The modules can be switched over by pressing “TIMER” key.
Fault Reset
Press “CONFIRM” and “CANCEL” keys for 5 seconds to reset
the faults manually.
Keylock
Press “TIMER” and “DOWN” icons for 5 seconds to enter
Keylock function. The “LOCK” icon will appear and all touch-
keys and the physical button will be disabled while the function
is activated.
Press “TIMER” and “DOWN” again to terminate the function.
Pump Circulation
Press “COOLING” key for 5 seconds in daily display to enter
Pump Circulation function. The “PUMP” icon will appear.
The pump will operate with no compressor running while this
function is activated.
Low Sound Mode
Press “CONFIRM” key for 5 seconds in temperature setting
display to enable Low Sound Mode. Press “FUNCTION” and
“CONFIRM” keys for 5 seconds in temperature setting display
to enable Night Low Sound Mode. In Night Low Sound Mode
the low sound function will only be activated during 21:00 to
6:00.
Manual Defrost
Press “COOLING” and “FUNCTION” keys for 5 seconds in
temperature setting display to enter Manual Defrost setting. The
modules can be selected by pressing “TIMER” and defrost will
begin once pressing “CONFIRM”.
Press “CANCEL” to terminate this setting.