FORM NO.:6U6K-B01E-NB-EN
JOHNSON CONTROLS
138
TABLE 49 – READ DATA
Short Name
(BACnet Object Name)
Data Type M odify
IP
Min
Valu
e
IP
Max
Value
IP
Units
IP
Display
Prec
SI Min
Value
SI Max
Values
SI
Units
SI
Display
Prec
Enum Set
BACoid
(Customer BAS
BACnet)
Chiller On|Off (Status) Boolean No None 1 None 1 BV100
System Status Enum No None 1 None 1
0-Cooling, 1-Heating,
8-Pump
MV101
Other Status Unsigned No None 1 None 1 AV102
HMI Communication St atus Boolean No Non e 1 None 1 BV103
Unit Network St atus (1-16) Unsigned No Non e 1 None 1 AV104
Unit Fault Sta
tus (1-16) Unsigned No None 1 None 1 AV109
Chiller EWT Float No °F 0.1 °C 0.1 AV110
Chiller LWT Float No °F 0.1 °C 0.1 AV111
Ambient Temp Float No °F 0.1 °C 0.1 AV113
Chiller Loading Float No % 0.1 % 0.1 AV114
Available Mode Enum No None 1 None 1 MV115
Total Run Hours Unsigned No Ho urs 1 Hours 1
0-Heat pump, 1 -
Cooling only
AV117
Unit Network St atus (17-32) Unsigned No None 1 None 1 AV121
Unit Fault Status (17-32) Unsigned No None 1 None 1 AV122
Unit Quantity Unsigned No None 1 None 1 AV123