SECTION 5 – TECHNICAL DATA
Notes
1. SYS1 oil type: FV68H;
2. SYS2 oil type: RL 32-3MAF;
3. Both of the systems are charged with additional oil before
delivery.
TABLE 10 - REFRIGERANT AND OIL CHARGE
Charge with proper oil for each system when
additional oil is required. Mix-ups of different oils
may cause compressor failure.
YMAA/YMPA 0045 0065 0080 0100 0130 0160 0200 0230 0260
Refrigerant
Charge
SYS1 kg 9.5 12.3 8.5 9.5 11.4 9.5 11 9.5 11.4
SYS2 kg / / 9.05 11 11.4 10 10.5 11 11.4
SYS3 kg / / / / / 10 10.5 11.4 11.4
SYS4 kg / / / / / / / 11.4 11.4
Tonnes of CO
2
Equivalent
(GWP)
CO
2
eq (t) 19.9 25.7 36.7 42.9 47.7 61.6 66.9 90.5 95.3
Oil Charge
SYS1 L 2.9 5 1.6 1.6 5 1.6 5 1.6 5
SYS2 L / / 5.6 5.6 5.6 5.6 5.6 5.6 5.6
SYS3 L / / / / / 5.6 5.6 5.6 5.6
SYS4 L / / / / / / / 5.6 5.6
Cooke Industries - Phone: +64 9 579 2185 Email: sales@cookeindustries.co.nz Web: www.cookeindustries.co.nz