SECTION 7 - OPERATION
JOHNSON CONTROLS
109
Form 201.28-NM1.1
Issue date: 08/06/2021
7
Building automation system (BAS)
communications
There are three different ways the chiller communi-
cates to the BAS.
Using board Native Communication protocol
Using an E-Link Gateway
Using an SC-EQ Communication Card
Using communications protocol
TB3 Port 1 Native BAS RS-485.
SW1 RS-485 Biasing Switch for Port. Set to ON if
chiller is in an End of Line position on the network.
U26 is the Port 1 RS-485 Driver Chip. It is
socketed to allow field replacement. RX1 and TX1 LEDs
illuminate to indicate Port 1 communications activity.
YVAA native communication setup
Native communication is applicable to three types of
protocols, they are BACnet, N2 and Modbus (RTU).
It requires IPU II Microboard (331-03478-101) and
software version Y.ACS.20.02 or later.
BACnet MS/TP setup port 1 (TB3)
To set up the BACNET MS/TP Port 1, complete the
following steps:
1. Connect the BACnet MS/TP Network to Port 1 on
the IPU II I/O Board.
2. Set up the YVAA Port 1 (P1) for BACnet Com-
munications as shown in Figure 27 on page 108.
To access the Port communication parameters:
1. Press the PROGRAM key once.
2. Enter password 5255.
3. Press the (ENTER) key to display the Port 1
(P1) settings.
Set the following parameters:
1. 
multiplied by 100): set as required by network.
2. 

(see 8).
3. P1 Protocol: set to BACNET (Default Setting).
4. P1 Manual MAC Address: set to 1
(Default Setting).
5. P1 Baud rate: set as required by network.
If not known set to AUTO.
6. P1 Parity: set to NONE (Default Setting).
7. P1 Stop Bits: set to 1 (Default Setting).
N2 Metasys setup port 1 (TB3)
1. Connect the N2 Network to Port 1 on the IPU II
I/O Board as shown in Figure 18 on page 104.
2. Set up the YVAA Port 1 (P1) for N2 Communica-
tions.
To access the communication parameters:
1. Press the PROGRAM key once
2. Enter password 5255
3. Press (ENTER) to display the Port 1 (P1)
settings.
Set the following parameters:
1. 
2. 
3. P1 Protocol: Set to N2
4. P1 Manual MAC Address: Set to 0-127 as
required by the parameters set in the BAS
network.
5. P1 Baud Rate: 9600
6. P1 Parity: None (Default Setting)
7. P1 Stop Bits1: (Default Setting)
The BACnet DE Instance (Device In-
stance) is determined by adding the [DE
MODIFIER AD-DRESS x 100] with the
DE MODIFIER OFFSET. That is, if the
desired DE Instance address is 5023, set
the DE Modier Address to 50, and then
set the DE Modier Oset to 23 (50 X
100 + 23 = 5023). DE Instances must be
limited to values between 1 and 4,194,303
and every device in the network must have
a unique Device Instance.
You must always cycle power to the mi-
croboard following port setting changes.