SECTION 7 - OPERATION
JOHNSON CONTROLS
115
Form 201.28-NM1.1
Issue date: 08/06/2021
7
Table 14 - YVAA native communications data map (Cont'd)
Imperial SI Point List Description 1 2 3 4 5 6 7 8 9 10
33 S2_HI_MTR_T AI25 538 03,04 x10 ADF 29 °F °C Sys 2 Highest M
otor Temperature S S S S S S
34 VSD_OUT_FR AI26 539 03,04 x10 ADF 30 Hz Hz VSD Output Fre
quency SSSSSS
35 VSD_CMD_FR AI27 540 03,04 x10 ADF 31 Hz Hz VSD Command Fr
equency S S S S S S
36 S1_COND_DR AI28 541 03,04 x10 ADF 32 % % Sys 1 Condenser Dr
ain Valve % Open S S S S S S
37 S2_COND_DR AI29 542 03,04 x10 ADF 33 % % Sys 2 Condenser Dr
ain Valve % Open S S S S S S
38 S1_OP_CODE AI30 543 03,04 x1 ADF 34 None None Sys 1 Operat
ional Code SSSSSS
39 S2_OP_CODE AI31 544 03,04 x1 ADF 35 None None Sys 2 Operat
ional Code SSSSSS
40 S1_FTL_CODE AI32 545 03,04 x1 ADF 36 None None Sys 1 Fault
Code SSSSSS
41 S2_FLT_CODE AI33 546 03,04 x1 ADF 37 None None Sys 2 Fault
Code SSSSSS
42 S1_FAN_STG AI34 547 03,04 x1 ADF 38 None None Sys 1 Conden
ser Fan Stage [0-14] S S S S S S
43 S2_FAN_STG AI35 548 03,04 x1 ADF 39 None None Sys 2 Conden
ser Fan Stage [0-14] S S S S S S
44 S1_FAN_SPD AI36 549 03,04 x1 ADF 40 % % Sys 1 Condenser Fan
Speed (VSD) OOOOOO
45 S2_FAN_SPD AI37 550 03,04 x1 ADF 41 % % Sys 2 Condenser Fan
Speed (VSD) OOOOOO
46 LEAD AI38 551 03,04 x1 ADF 42 None None Lead System
SSSSSS
47 LCHLT_SETP AI39 552 03,04 x10 ADF 43 °F °C Leaving Chilled
Liquid Setpoint S S S S S S
48 LCHLT_CUTOUT AI40 553 03,04 x10 ADF 44 °F °C Leaving Chill
ed Liquid Cutout S S S S S S
49 S1_ECON_VLV AI41 554 03,04 x10 ADF 45 % % Sys 1 Economizer
Valve % Open SSSSSS
50 S2_ECON_VLV AI42 555 03,04 x10 ADF 46 % % Sys 2 Economizer
Valve % Open SSSSSS
51 SUCT_PRS_CUT AI43 556 03,04 x10 ADF 47 PSI BAR Suction Pre
ssure Cutout S S S S S S
52 VSD_DCB_VT AI44 557 03,04 x1 ADF 48 Volts Volts
VSD DC Bus Voltage (Unit)
VSD DC Bus Voltage Sys 1 (Frame E/F)
SSSSSS
53 VSD_DCB_VT2 AI45 558 03,04 x1 ADF 49 Volts Volts VSD DC B
us Voltage Sys 2 (Frame E/F) O O O O O O
54 REM_SETPOINT AI46 559 03,04 x10 ADF 50 °F °C Remote Leavin
g Chilled Liquid Setpoint S S S S S S
55 S1_SUBCOOL AI47 560 03,04 x10 ADF 51 °F (diff) °C (diff)
Sys 1 Subcooling (Microchannel) O O O O O O
56 S1_EVAP_LL AI48 561 03,04 x10 ADF 52 % % Sys 1 Evaporator L
iquid Level (Round Tube) S S S S S S
57 S2_SUBCOOL AI49 562 03,04 x10 ADF 53 °F (diff) °C (diff)
Sys 2 Subcooling (Microchannel) O O O O O O
58 S2_EVAP_LL AI50 563 03,04 x10 ADF 54 % % Sys 2 Evaporator L
iquid Level (Round Tube) S S S S S S
59 COOLING_RNG AI51 564 03,04 x10 ADF 55 °F °C Cooling Range
SSSSSS
60 S1_DSC_SHEAT AI52 565 03,04 x10 ADF 56 °F (diff) °C (dif
f) Sys 1 Discharge Superheat S S S S S S
61 S2_DSC_SHEAT AI53 566 03,04 x10 ADF 57 °F (diff) °C (dif
f) Sys 2 Discharge Superheat S S S S S S
62 S1_SYS_STATE AI54 567 03,04 x1 ADF 58 None None
Sys 1 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
SSSSSS
63 S2_SYS_STATE AI55 568 03,04 x1 ADF 59 None None
Sys 2 System State [0=Stopped, 1=Running, 2=Faulted,
4=Locked Out, 5=Pre-Run
SSSSSS
64 S1_MTR_OVER AI56 569 03,04 x1 ADF 60 Amps Amps Sys 1 Motor
Current Overload Setting S S S S S S
65 S2_MTR_OVER AI57 570 03,04 x1 ADF 61 Amps Amps Sys 2 Motor
Current Overload Setting S S S S S S
66 FAN_TYPE AI58 571 03,04 x1 ADF 62 None None
Condenser Fan Control Type [1=Std. VSD, 2=Opt. VSD,
3=Std. Staged, 4=Opt. Staged, 5=Std. VSD with Interlock,
6=Opt. VSD with Interlock, 7 = Opt. ENH, 8 = Opt. ENH
XL]
SSSSSS
67 FC_MODE AI59 572 03,04 x1 ADF 63 None None
Free Cooling Mode [0=Mech, 1=Free Cool, 2=Hybrid]
(Free Cooling)
OOOOOO
68 FC_CTRL AI60 573 03,04 x1 ADF 64 % %
Free Cooling Control Programmed [0=Disabled, 1=Open
Loop, 2=Closed Loop] (Free Cooling)
NOOOOO
69 CC_BYP_VALVE AI61 574 03,04 x10 ADF 65 % % Cooling Coil B
ypass Valve (Free Cooling Closed Loop) N O O O O O
70 CC_VALVE AI62 575 03,04 x10 ADF 66 % % Cooling Coil Valve
(Free Cooling Closed Loop) N O O O O O
71 CC_TEMP AI63 576 03,04 x10 ADF 67 °F °C Cooling Coil Temp
erature (Free Cooling Closed Loop) N O O O O O
72
HX_LEAVE_TEMP
AI64 577 03,04 x10 ADF 68 °F °C
Heat Exchanger Leaving Temperature (Free Cooling
Closed Loop)
NOOOOO
73
HX_ENTER_TEMP
AI65 578 03,04 x10 ADF 69 °F °C
Heat Exchanger Entering Temperature (Free Cooling
Closed Loop)
NOOOOO
BACnet Name
BACnet
Object
Instance
Modbus
Address
Modbus Data Type
Supported
Modbus
Scaling
(See
Note 5)
N2 Metasys
Engineering Units Point List Code: S = Standard O = Optional N = Not Available
Item
Ref
Num
YVAA YVFA YAGK Native 13 May 21
Property of Johnson Controls