SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
MESSAGE DESCRIPTION
Harmonic Filter – High
Total Demand
Distortion
The control center determines this shutdown by using data supplied from the harmonic lter logic
board. This shutdown indicates that the lter is not operating correctly or the input current to
the drive/lter system is not sinusoidal. This shutdown will occur if the Total Demand Distortion
(TDD) in any one phase exceeds 25% continuously for 45 seconds. TDD is an acronym for Total
Demand Distortion, a term dened by the IEEE Std 519-1992 standard as “the total root - sum
- square harmonic current distortion, in percent of the maximum demand load current (15 or 30
min demand)”. .
TABLE 12 - SAFETY SHUTDOWN MESSAGES (CONT'D)