SECTION 6 - PRINTING
FIGURE 52 - SAMPLE PRINTOUT (STATUS OR HISTORY)
LD26759
YYORK HISTORY 1
JCI GLENDALE
YZ-MA033AN030P042A
16-885000-5
YK CHILLER ID 0
(C) 1997 - 2014 YORK, A JOHNSON CONTROLS COMPANY
TUE 29 AUG 2017 9:52:26 AM
SYSTEM RUN
MBC - FAULT CONTACTS OPEN
CONTROLS Y.OPT.01.05.308
RUN TIME 0 DAYS 23 HR 0 MIN 27 SEC
OPERATING HOURS
NUMBER OF STARTS
ACTIVE RUN COMMAND
CAPACITY CONTROL
------------------------------------------------------
CONTROL STATE = COOLING CONTROL
LOAD LIMIT = NONE
VSD FREQUENCY COMMAND = 138.07 HZ
VSD OUTPUT FREQUENCY = 138.05 HZ
VSD CONTROL MODE = INACTIVE
ACTIVE ANTI-SURGE MINIMUM = 120.62 HZ
ANTI-SURGE MINIMUM FREQUE = 120.45 HZ
ANTI-SURGE TRANSIENT OFFS = 0.00 HZ
VGD COMMAND = 100.00 %
VGD POSITION = 100.00 %
VGD CONTROL MODE = AUTO
HGBP CONTROL MODE = AUTO
HEAD PRESSURE = 9.7 PSID
SURGE MARGIN ADJUST = 0.0 HZ
VSD START FREQUENCY = 111.45 HZ
MAPPING ENABLE = 5.0 ~F
ACC SURGE COUNT = 4587590
EVAPORATOR
------------------------------------------------------
CHILLED LIQUID PUMP = RUN
CHILLED LIQUID FLOW SWITC = CLOSED
ACTIVE COOLING SETPOINT = 42.0 ~F
SHUTDOWN TEMPERATURE = 34.0 ~F
LEAVING CHILLED LIQUID TE = 41.9 ~F
ENTERING CHILLED LIQUID T = 53.5 ~F
EVAPORATOR PRESSURE = 8.5 PSIA
EVAPORATOR SATURATION TEM = 40.4 ~F
EVAPORATOR SMALL TEMP DIF = 1.5 ~F
CONDENSER
------------------------------------------------------
CONDENSER LIQUID PUMP = RUN
CONDENSER LIQUID FLOW SWI = CLOSED
LEAVING CONDENSER LIQUID = 75.5 ~F
ENTERING CONDENSER LIQUID = 67.6 ~F
CONDENSER PRESSURE = 18.2 PSIA
CONDENSER SATURATION TEMP = 75.4 ~F
CONDENSER SMALL TEMP DIFF = -0.1 ~F
CONDENSER REFRIGERANT TEM = 75.9 ~F
DROP LEG REFRIGERANT TEMP = 68.5 ~F
SUBCOOLING TEMPERATURE = 6.9 ~F
Head Pressure = 9.7 PSID
Head Pressure Setpoint = 23.0 PSID
PID Control Mode = Inactive
Control Valve Command = 0.0 %
Compressor
------------------------------------------------------
Motor Speed = -1.20 Hz
Discharge Temperature = 84.7 ~F
Discharge Superheat = 9.4 ~F
Adjusted Discharge Superh = 9.4 ~F
Discharge Superheat Limit = 11.1 ~F
Discharge Superheat Limit = No
Surge
-----------------------------------------------------
Surge Avoidance Surge Cou = 0
Delta P / P = 1.14
Surge Window Time = 3 Min
Surge Window Count = 0
Surge Detection State = State 3
Condenser Refrigerant Level Control
-----------------------------------------------------
Condenser Refrigerant Lev = 47.6 %
Condenser Active Level Se = 45.0 %
Condenser Level Control S = PID Control
Condenser Level Control V = 23.5 %
Subcooler Effectiveness = 0.884
Variable Geometry Diffuser
-----------------------------------------------------
Stall Detector Voltage = 0.24 V
Mach Number = 0.000
Discharge Pressure = 18.5 PSIA
Stall Time = 0 Days 0 Hr 0 Min 0 Sec
VGD Feedback Counts = 29945
VGD Fault Code = 0000 0000 0000 0000
Variable Speed Drive
-----------------------------------------------------
Motor Run = On
Motor % Full Load Amps = 60.8 %
Full Load Amps = 362 A
Precharge Relay Output = Off
Trigger SCR Output = On
Cooling System = On
kW Hours = 76921 kWh
Input Power = 209 kW
Output Frequency = 138.05 Hz
Max Chiller Frequency = 178.33 Hz
Output Voltage = 362 V
DC Bus Voltage = 637 V
DC Inverter Link Current = 245 A
Phase A Output Current = 216 A
Phase B Output Current = 220 A
Phase C Output Current = 216 A
Internal Ambient Temperat = 80 ~F
Converter Heatsink Temper = 75 ~F
Phase A Baseplate Tempera = 103 ~F
Phase B Baseplate Tempera = 101 ~F
Phase C Baseplate Tempera = 98 ~F
Manual DC Bus = Disabled
Manual VSD Cooling = Disabled
ID Faults = 0
Checksum Errors = 0
Error Packets = 0
Timeout Faults = 162
Motor Cooling
-----------------------------------------------------
Motor Winding Phase A1 Te = 32.0 ~F
Motor Winding Phase B1 Te = 32.0 ~F
Motor Winding Phase C1 Te = 32.0 ~F
Motor Winding Phase A2 Te = 32.0 ~F
Motor Winding Phase B2 Te = 32.0 ~F
Motor Winding Phase C2 Te = 32.0 ~F
Average Winding Temperatu = 32.0 ~F
Motor Housing Temperature = 103.4 ~F
Motor Housing Temperature = 80.0 ~F
Motor Cooling Valve Comma = 0.0 %
Motor Cooling Control Sta = Dual PID Control