EasyManua.ls Logo

York YZF024THRU 060*C - Heating Performance Data; Heating Performance with Air Handler Coils

York YZF024THRU 060*C
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Johnson Controls Unitary Products
632151-YTG-A-1010
\
* Notates “Hot Heat Pump” performance. These ratings are not AHRI Listed.
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the
total electric power input during the same period.
— = Not Applicable.
HEATING PERFORMANCE - With Air Handler
UNIT
MODEL*
AIR
HANDLER
COIL
1
MODEL
ARI HEATING
2
RATED
CFM
47F17FHSPF
MBH COP KW MBH COP KW STD
1 PH HP WITH MV - VARIABLE SPEED
YZF02413(C)
MV12B FC/MC35B 80024.03.821.8415.02.541.738.50
MV12B FC/MC43B 80024.04.021.7614.92.701.629.00
YZF03013(C)
MV12B FC/MC43B 1000 29.6 3.94 2.20 19.1 2.74 2.04 9.00
MV16C FC/MC43C 1000 29.6 3.96 2.19 19.0 2.76 2.02 9.00
YZF03613(C)
MV12D FC/MC48D
116036.03.982.6523.22.802.439.00
1000 36.0 3.40 3.29 23.2 2.80 2.43 9.00
MV16C FC/MC48C
1200 36.0 3.92 2.71 23.4 2.76 2.48 9.00
1000 36.0 3.40 3.35 23.4 2.76 2.48 9.00
MV12D FC/MC60D
113536.04.102.6023.22.862.389.00
1000 36.0 3.40 3.24 23.2 2.86 2.38 9.00
YZF04213(C) MV20D FC/MC62D
1400 37.8 3.86 2.87 25.2 2.68 2.76 9.00
1020 37.1 3.63 2.75 25.2 2.68 2.76 8.78
YZF04813(C)
MV20D FC/MC62D
1630 48.0 3.78 3.91 33.6 2.70 3.65 9.00
1000 48.0 3.29 4.38 33.6 2.70 3.65 9.00
MV20D FC64D
1630 48.0 3.94 3.79 34.0 2.78 3.58 9.00
1000 48.0 3.45 4.26 34.0 2.78 3.58 9.00
1 PH HP WITH AV / SV / F*FV - VARIABLE SPEED
YZF02413(C) AV*36
725
23.83.921.7814.82.661.639.00
505*
YZF03013(C) AV*36
96029.44.022.1418.92.801.989.00
72528.93.752.2618.92.801.989.00
YZF03613(C) AV*48
1220 36.0 4.20 2.55 23.2 2.92 2.33 9.00
96036.03.403.1923.22.922.339.00
1 PH HP WITH AHP / SHP / AHX / F*FP
YZF02413(C)
AHX30
83524.03.881.8315.12.561.738.50
61823.83.631.9215.12.561.738.50
AHX36
82024.03.901.8215.12.621.698.50
60023.83.651.9115.12.621.698.50
F6FP030 85024.03.821.8615.22.541.758.50
F6FP036 85524.03.901.8015.12.581.718.50
YZF03013(C) AHX36
1005 29.6 4.00 2.17 19.0 2.78 2.00 9.00
75529.13.732.2819.02.782.009.00
YZF03613(C)
AHX42
1200 36.0 4.00 2.65 23.2 2.80 2.43 9.00
1000 36.0 3.40 3.29 23.2 2.80 2.43 9.00
AHX48
1255 36.0 4.08 2.60 23.2 2.82 2.41 9.00
1080 36.0 3.40 3.24 23.2 2.82 2.41 9.00
F6FP042 1290 36.0 4.06 2.64 23.4 2.80 2.45 9.00
F6FP048 112536.04.122.5723.02.902.329.00
YZF04213(C)
AHX60
1440 37.8 3.88 2.85 25.6 2.72 2.76 9.00
1040 37.1 3.65 2.73 25.6 2.72 2.76 8.78
F6FP060 1475 38.0 3.86 2.88 25.4 2.68 2.78 9.00
YZF04813(C)
AHX60
1570 48.0 3.82 3.84 33.4 2.72 3.60 9.00
98548.03.334.3033.42.723.609.00
F6FP060 1570 48.0 3.82 3.84 33.4 2.72 3.60 9.00
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no sup-
plemental electric heat operation.