5742637-YIM-D-0620
20 Johnson Controls Ducted Systems
060
(5.0)
208-3-60 16 110 24.9 4.4 6.8 0
NONE - - - 31.2 40
E05 4 1 11.1 31.2 40
E07 5.6 1 15.5 31.2 40
E10 8 1 22.2 36.3 45
E15 11.9 2 33 49.8 50
E20 15.9 2 44.1 63.7 70
E30 22.2 2 61.6 85.5 90
230-3-60 16 110 24.9 4.4 6.8 0
NONE - - - 31.2 40
E05 5.3 1 12.7 31.2 40
E07 7.5 1 18 31.2 40
E10 10.6 1 25.5 40.4 45
E15 15.9 2 38.2 56.3 60
E20 21.2 2 51 72.2 80
E30 29.6 2 71.2 97.5 100
460-3-60 7.8 52 12.1 4.4 3.15 0
NONE - - - 15.1 20
E07 6.8 1 8.2 15.1 20
E10 10.1 1 12.1 19.1 20
E15 13.6 2 16.4 24.4 25
E20 19.5 2 23.5 33.3 35
E30 28.8 2 34.6 47.2 50
575-3-60 5.7 38.9 8.9 4.4 2.2 0
NONE - - - 11.1 15
E10 10.6 1 10.2 15.5 20
E15 15.9 2 15.3 21.9 25
E20 21.2 2 20.4 28.2 30
E30 30.4 2 29.3 39.3 40
072
(6)
208-3-60 19.6 136 27 4.4 8.3
None - - - 37.2 50
E05 4 1 11.1 37.2 50
E07 5.6 1 15.5 37.2 50
E10 8 1 22.2 38.1 50
E15 11.9 1 33 51.6 60
E20 15.9 2 44.1 65.5 70
E30 22.2 2 61.6 87.4 90
230-3-60 19.6 136 27 4.4 8.3
None - - - 37.2 50
E05 5.3 1 12.7 37.2 50
E07 7.5 1 18 37.2 50
E10 10.6 1 25.5 42.3 50
E15 15.9 1 38.2 58.1 60
E20 21.2 2 51 74.1 80
E30 29.6 2 71.2 99.4 100
460-3-60 9.4 66.1 13 2.4 4.1
None - - - 18.3 25
E07 6.8 1 8.2 18.3 25
E10 10.1 1 12.1 20.3 25
E15 13.6 1 16.4 25.6 30
E20 19.5 2 23.5 34.5 35
E30 28.8 2 34.6 48.4 50
575-3-60 7.1 55.3 10 4.4 3.2
None - - - 13.9 20
E10 10.6 1 10.2 16.8 20
E15 15.9 1 15.3 23.1 25
E20 21.2 2 20.4 29.5 30
E30 30.4 2 29.3 40.6 45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Single phase, high static belt drive motors not available on gas heating units.
ZE036-072 - Without Powered Convenience Outlet (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Accessory
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps