EasyManua.ls Logo

York ZE Series - Electrical Data: Single-Phase Gas Heat, Belt Drive

York ZE Series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5742637-YIM-D-0620
Johnson Controls Ducted Systems 29
Table 8: Electrical data: single-phase gas heat, belt drive
ZE036-060 - Without Powered Convenience Outlet (Belt Drive Single Phase Gas Heat)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Accessory
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
036
(3)
208-1-60 15.4 83.9 24 2.3 17.4 None - - - 39.5 50
230-1-60 15.4 83.9 24 2.3 17.4 None - - - 39.5 50
048
(4)
208-1-60 19.6 130 31 2.3 17.4 None - - - 44.2 60
230-1-60 19.6 130 31 2.3 17.4 None - - - 44.2 60
060
(5)
208-1-60 24.4 144.2 38 4.4 17.4 None - - - 52.3 70
230-1-60 24.4 144.2 38 4.4 17.4 None - - - 52.3 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZE036-060 - With Powered Convenience Outlet (Belt Drive Single Phase Gas Heat)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Accessory
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
036
(3)
208-1-60 15.4 83.9 24 2.3 17.4 20 None - - - 49.5 60
230-1-60 15.4 83.9 24 2.3 17.4 20 None - - - 49.5 60
048
(4)
208-1-60 19.6 130 31 2.3 17.4 20 None - - - 54.2 70
230-1-60 19.6 130 31 2.3 17.4 20 None - - - 54.2 70
060
(5)
208-1-60 24.4 144.2 38 4.4 17.4 20 None - - - 62.3 80
230-1-60 24.4 144.2 38 4.4 17.4 20 None - - - 62.3 80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

Table of Contents

Other manuals for York ZE Series

Related product manuals