251934-YTG-J-0910
Johnson Controls Unitary Products 73
300
(25)
208-3-60 23.0 160 31.5 3.7 28.0 10.0
None - - - 151.8 175
E18 13.5 1 37.5 151.8 175
E36 27.0 2 74.9 151.8 175
E54 40.6 2 112.7 188.4 200
E72 54.1 2 150.2 197.7 200
230-3-60 23.0 160 31.5 3.7 26.0 10.0
None - - - 149.3 175
E18 18.0 1 43.3 149.3 175
E36 36.0 2 86.6 153.3 175
E54 54.0 2 129.9 174.9 175
E72 72.0 2 173.2 218.2 225
460-3-60 12.2 87 17.1 1.9 13.0 5.0
None - - - 77.7 90
E18 18.0 1 21.7 77.7 90
E36 36.0 2 43.3 77.7 90
E54 54.0 2 65.0 87.5 90
E72 72.0 2 86.6 109.1 110
575-3-60 8.7 62 13.5 1.5 10.3 4.0
None - - - 57.7 60
E18 18.0 1 17.3 57.7 60
E36 36.0 2 34.6 61.2 70
E54 54.0 2 52.0 69.8 70
E72 72.0 2 69.3 87.2 90
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZJ180-300 - Standard Drive With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps

Other manuals for York ZF SERIES