5464597-YIM-B-0518
22 Johnson Controls Ducted Systems
120
(10)
208 14.6 110 22 3.03 6.8 5.5
None-- -45.851.360 60
E18 13.5 2 37.5 55.4 62.3 60 70
E24 18 2 50 71 77.9 80 80
E36 25.5 2 70.8 97 103.9 100 110
E54 40.6 2 112.7 149.4 156.3 150 175
230 14.6 110 22 3.03 6.8 5.5
None-- -45.851.360 60
E18 18 2 43.3 62.6 69.5 70 70
E24 24 2 57.7 80.6 87.5 90 90
E36 34 2 81.8 110.8 117.6 125 125
E54 54 2 129.9 138.4 145.3 150 175
460 7.4 55 12 1.6 3.4 2.2
None-- -23.325.530 30
E18 18 2 21.7 31.4 34.1 35 35
E24 24 2 28.9 40.4 43.1 45 45
E36 34 2 40.9 55.4 58.1 60 60
E54 54 2 65 69.3 72 80 80
575 5.6 43 9 1.35 2.4 1.8
None-- -17.719.520 25
E18 18 2 17.3 24.6 26.9 25 30
E24 24 2 23.1 31.9 34.1 35 35
E36 34 2 32.7 43.9 46.1 45 50
E54 54 2 52 55 57.3 60 60
150
(12.5)
208 23.1 160 36 3.03 9.6 5.5
None - - - 73.7 79.2 90 100
E18 13.5 2 37.5 73.7 79.2 90 100
E24 18 2 50 74.5 81.4 90 100
E36 25.5 2 70.8 100.5 107.4 110 110
E54 40.6 2 112.7 152.9 159.8 175 175
230 23.1 160 36 3.03 9.6 5.5
None - - - 73.7 79.2 90 100
E18 18 2 43.3 73.7 79.2 90 100
E24 24 2 57.7 84.1 91 90 100
E36 34 2 81.8 114.3 121.1 125 125
E54 54 2 129.9 141.9 148.8 175 175
460 12.2 87 19 1.6 4.7 2.2
None-- -38.640.850 50
E18 18 2 21.7 38.6 40.8 50 50
E24 24 2 28.9 42 44.8 50 50
E36 34 2 40.9 57 59.8 60 60
E54 54 2 65 70.9 73.6 80 80
575 8.7 62 14 1.35 3.6 1.8
None-- -28.630.435 35
E18 18 2 17.3 28.6 30.4 35 35
E24 24 2 23.1 33.4 35.6 35 40
E36 34 2 32.7 45.4 47.6 50 50
E54 54 2 52 56.5 58.8 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF078-150 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Max Fuse
2
/
Breaker
3
Size w/
Pwr Exh
(Amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps