5464597-YIM-B-0518
24 Johnson Controls Ducted Systems
120
(10)
208 14.6 110 22 3.03 9.6 5.5
None - - - 48.6 54.1 60 60
E18 13.5 2 37.5 58.9 65.8 60 70
E24 18 2 50 74.5 81.4 80 90
E36 25.5 2 70.8 100.5 107.4 110 110
E54 40.6 2 112.7 152.9 159.8 175 175
230 14.6 110 22 3.03 9.6 5.5
None - - - 48.6 54.1 60 60
E18 18 2 43.3 66.1 73 70 80
E24 24 2 57.7 84.1 91 90 100
E36 34 2 81.8 114.3 121.1 125 125
E54 54 2 129.9 141.9 148.8 175 175
460 7.4 55 12 1.6 4.7 2.2
None - - - 24.6 26.8 30 30
E18 18 2 21.7 33 35.8 35 40
E24 24 2 28.9 42 44.8 45 45
E36 34 2 40.9 57 59.8 60 60
E54 54 2 65 70.9 73.6 80 80
575 5.6 43 9 1.35 3.6 1.8
None - - - 18.9 20.7 20 25
E18 18 2 17.3 26.1 28.4 30 30
E24 24 2 23.1 33.4 35.6 35 40
E36 34 2 32.7 45.4 47.6 50 50
E54 54 2 52 56.5 58.8 70 70
150
(12.5)
208 23.1 160 36 3.03 14 5.5
None - - - 78.1 83.6 100 100
E18 13.5 2 37.5 78.1 83.6 100 100
E24 18 2 50 80 86.9 100 100
E36 25.5 2 70.8 106 112.9 110 125
E54 40.6 2 112.7 158.4 165.3 175 175
230 23.1 160 36 3.03 14 5.5
None - - - 78.1 83.6 100 100
E18 18 2 43.3 78.1 83.6 100 100
E24 24 2 57.7 89.6 96.5 100 100
E36 34 2 81.8 119.8 126.6 125 150
E54 54 2 129.9 147.4 154.3 175 175
460 12.2 87 19 1.6 6.6 2.2
None - - - 40.5 42.7 50 50
E18 18 2 21.7 40.5 42.7 50 50
E24 24 2 28.9 44.4 47.1 50 50
E36 34 2 40.9 59.4 62.1 60 70
E54 54 2 65 73.3 76 80 90
575 8.7 62 14 1.35 5.2 1.8
None - - - 30.2 32 35 40
E18 18 2 17.3 30.2 32 35 40
E24 24 2 23.1 35.4 37.6 40 40
E36 34 2 32.7 47.4 49.6 50 50
E54 54 2 52 58.5 60.8 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Max Fuse
2
/
Breaker
3
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps