EasyManua.ls Logo

York ZT SERIES - Page 32

York ZT SERIES
87 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6021980-UIM-A-1120
32 Johnson Controls Ducted Systems
150
(12.5)
208 17.6 17.6 136 136 27 27 3.5 14 5.5 20
None - - - 77.6 83.1 90 100
E18 13.5 2 37.5 77.6 83.8 90 100
E24 18 2 50 92.5 99.4 100 100
E36 25.5 2 70.8 118.5 125.4 125 150
E54 40.6 2 112.7 170.9 177.8 175 200
230 17.6 17.6 136 136 27 27 3.5 14 5.5 20
None - - - 77.6 83.1 90 100
E18 18 2 43.3 84.1 91 90 100
E24 24 2 57.7 102.1 109 110 110
E36 34 2 81.8 132.3 139.1 150 150
E54 54 2 129.9 159.9 166.8 175 175
460 8.5 8.5 66.1 66.1 13 13 1.6 6.6 2.2 20
None - - - 37.1 39.3 45 45
E18 18 2 21.7 41.6 44.4 45 45
E24 24 2 28.9 50.6 53.4 60 60
E36 34 2 40.9 65.6 68.4 70 70
E54 54 2 65 79.5 82.3 90 90
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZT078-150 high static indoor blower - with powered convenience outlet (Continued)
Size
(tons)
Volt
Compressors (each) OD fan
motors
(each)
Supply
blower
motor
Pwr
exh.
motor
Pwr
conv.
outlet
Electric heat option
MCA
1
(amps)
MCA
1
with pwr
exhaust
(amps)
Max fuse
2
/
breaker
3
size
(amps)
Max fuse
2
/
breaker
3
size with
pwr exh.
(amps)
RLA LRA MCC
C1 C2 C1 C2 C1 C2 FLA FLA FLA FLA Model kW Stages Amps

Table of Contents

Other manuals for York ZT SERIES

Related product manuals