EasyManua.ls Logo

York ZT SERIES - Page 53

York ZT SERIES
87 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6021980-UIM-A-1120
Johnson Controls Ducted Systems 53
ZT150 (12.5 Ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied drive Standard 3 HP and drive
3200 736 0.44 774 0.79 816 1.12 861 1.41 910 1.68 960 1.92 1012 2.15 1065 2.36 1118 2.57 1171 2.77
3400 751 0.64 789 1.00 831 1.32 877 1.61 925 1.88 975 2.13 1027 2.35 1080 2.57 1133 2.77 1186 2.98
3600 768 0.87 806 1.22 848 1.55 894 1.84 942 2.11 992 2.35 1044 2.58 1097 2.79 1150 3.00 1203 3.20
3800 787 1.11 825 1.47 867 1.79 913 2.09 961 2.35 1011 2.60 1063 2.83 1116 3.04 1169 3.25 1222 3.45
4000 808 1.38 846 1.74 888 2.06 933 2.35 982 2.62 1032 2.86 1084 3.09 1137 3.31 1190 3.51 1242 3.71
4200 830 1.67 868 2.03 910 2.35 956 2.64 1004 2.91 1054 3.15 1106 3.38 1159 3.59 1212 3.80 1265 4.00
4400 854 1.98 892 2.33 934 2.66 980 2.95 1028 3.21 1078 3.46 1130 3.69 1183 3.90 1236 4.11 1289 4.31
4600 880 2.30 918 2.66 960 2.98 1005 3.28 1053 3.54 1104 3.79 1156 4.01 1209 4.23 1262 4.43 1314 4.64
4800 907 2.65 945 3.01 987 3.33 1032 3.62 1081 3.89 1131 4.13 1183 4.36 1236 4.58 1289 4.78 1341 4.98
5000 935 3.01 973 3.37 1015 3.69 1061 3.99 1109 4.25 1160 4.50 1212 4.73 1264 4.94 1317 5.15 1370 5.35
5200 965 3.40 1003 3.75 1045 4.08 1091 4.37 1139 4.64 1190 4.88 1242 5.11 1294 5.32 1347 5.53 1400 5.73
5400 996 3.80 1034 4.16 1076 4.48 1122 4.77 1170 5.04 1221 5.28 1273 5.51 1326 5.72 - - - -
5600 1029 4.22 1067 4.57 1109 4.90 1155 5.19 1203 5.46 1253 5.70 - - - - - - - -
5800 1063 4.65 1101 5.01 1143 5.33 1188 5.62 - - - - - - - - - - - -
6000 1098 5.10 1136 5.46 - - - - - - - - - - - - - - - -
6200 1134 5.57 - - - - - - - - - - - - - - - - - -
High static 5 HP and drive 5 HP and field supplied drive