5167821-YTG-K-1118
Johnson Controls Ducted Systems 21
ZT037-150 unit limitations
Size
(tons)
Model Unit voltage
Unit limitations
Applied voltage Outdoor DB temp.
Minimum Maximum Maximum (°F)
037
(3)
ZT
208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125
049
(4)
ZT
208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125
061
(5)
ZT
208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125
078
(6.5)
ZT
208/230-3-60
187 252 125
460-3-60
432 504 125
090
(7.5)
ZT
208/230-3-60
187 252 125
460-3-60
432 504 125
102
(8.5)
ZT
208/230-3-60
187 252 125
460-3-60
432 504 125
120
(10)
ZT
208/230-3-60
187 252 125
460-3-60
432 504 125
150
(12.5)
ZT
208/230-3-60
187 252 125
460-3-60
432 504 125