5167821-YTG-K-1118
Johnson Controls Ducted Systems 27
115°F 125°F
1000
77 50.2 4.1 23.4 19.6 15.9 - - - 44.7 4.5 21.9 18.3 14.6 - - -
72 45.9 4.0 31.8 26.6 21.5 16.4 - - 41.8 4.5 30.4 25.2 20.0 14.9 - -
67 41.6 4.0 40.1 33.7 27.2 21.9 16.5 - 39.0 4.4 38.9 32.2 25.4 20.1 14.8 -
62 40.4 4.0 40.4 36.6 32.9 27.3 21.7 16.2 38.0 4.5 37.9 34.4 30.8 25.4 19.9 14.5
1200
77 50.0 4.1 28.1 21.8 15.5 - - - 44.9 4.5 26.4 20.2 14.0 - - -
72 46.6 4.0 34.9 28.7 22.5 16.3 - - 42.6 4.5 33.2 27.0 20.8 14.6 - -
67 43.1 4.0 41.8 35.6 29.5 23.0 16.6 - 40.4 4.4 40.1 33.9 27.7 21.3 14.8 -
62 42.4 4.0 42.1 39.3 36.4 29.8 23.1 16.4 39.7 4.5 39.5 37.0 34.5 27.9 21.2 14.6
57 41.6 4.1 41.6 41.6 41.6 36.5 29.6 22.7 39.1 4.6 38.8 38.8 38.8 34.5 27.6 20.8
1400
77 49.9 4.1 32.7 24.0 15.2 - - - 45.0 4.5 30.9 22.1 13.3 - - -
72 47.3 4.0 38.1 30.8 23.5 16.2 - - 43.4 4.5 36.1 28.9 21.6 14.4 - -
67 44.7 4.0 43.4 37.6 31.8 24.2 16.7 - 41.7 4.5 41.2 35.6 29.9 22.4 14.9 -
62 44.3 4.0 43.9 41.9 40.0 32.2 24.4 16.6 41.5 4.5 41.0 39.6 38.2 30.4 22.5 14.7
57 43.9 4.1 43.9 43.9 43.9 40.3 32.2 24.2 41.2 4.6 40.7 40.7 40.7 38.4 30.2 22.1
1600
77 49.7 4.1 37.4 26.1 14.9 - - - 45.2 4.5 35.5 24.1 12.7 - - -
72 48.0 4.1 41.2 32.8 24.4 16.1 - - 44.2 4.5 38.9 30.7 22.4 14.2 - -
67 46.2 4.0 45.0 39.5 34.0 25.4 16.7 - 43.1 4.5 42.4 37.3 32.2 23.5 14.9 -
62 46.2 4.0 45.6 44.6 43.6 34.7 25.8 16.9 43.2 4.5 42.5 42.2 41.9 32.9 23.8 14.8
57 46.2 4.1 46.2 46.2 46.2 44.0 34.9 25.7 43.3 4.5 42.6 42.6 42.6 42.3 32.8 23.3
1800
72 48.7 4.1 44.4 34.9 25.4 15.9 - - 45.0 4.5 41.8 32.5 23.2 13.9 - -
67 47.7 4.1 46.7 41.5 36.3 26.6 16.8 - 44.5 4.5 43.5 39.0 34.4 24.7 14.9 -
62 48.1 4.1 47.3 47.3 47.2 37.2 27.1 17.1 45.0 4.5 44.0 44.0 44.0 35.4 25.1 14.9
57 48.5 4.1 48.0 48.0 48.0 47.8 37.5 27.2 45.4 4.5 44.5 44.5 44.5 44.5 35.4 24.6
2000
72 49.5 4.1 47.5 37.0 26.4 15.8 - - 45.8 4.5 - 34.3 24.0 13.7 - -
67 49.3 4.1 48.3 43.4 38.6 27.7 16.9 - 45.9 4.5 - 40.7 36.7 25.8 14.9 -
62 50.1 4.1 49.1 49.1 49.1 39.6 28.5 17.4 46.7 4.5 - 45.5 45.5 37.9 26.4 15.0
57 50.9 4.0 49.9 49.9 49.9 49.9 40.1 28.7 47.6 4.5 - 46.4 46.4 46.4 38.0 25.9
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBh = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT049 high speed compressor (4.0 ton) (continued)
Air on evaporator
coil
Temperature of air on condenser coil
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
CFM
WB
(°F)
Return dry bulb (°F) Return dry bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65