5167821-YTG-K-1118
Johnson Controls Ducted Systems 31
115°F 125°F
1250
77 63.5 5.4 32.6 27.3 21.9 - - - 56.7 6.1 30.5 24.9 19.2 - - -
72 57.9 5.3 41.4 34.9 28.3 21.8 - - 53.0 5.9 39.3 32.6 25.9 19.3 - -
67 52.3 5.2 50.1 42.4 34.7 28.3 21.8 - 49.4 5.8 48.0 40.3 32.6 26.1 19.5 -
62 50.2 5.1 49.0 45.1 41.1 34.7 28.2 21.8 46.8 5.7 45.5 42.4 39.4 32.9 26.5 20.0
1500
77 62.3 5.4 36.6 28.7 20.8 - - - 55.7 6.0 34.5 26.3 18.0 - - -
72 58.0 5.3 44.1 36.5 29.0 21.4 - - 53.1 5.9 41.8 34.2 26.6 18.9 - -
67 53.6 5.2 51.6 44.4 37.2 29.4 21.6 - 50.5 5.8 49.1 42.1 35.1 27.2 19.3 -
62 51.8 5.1 50.6 48.0 45.4 37.4 29.3 21.3 48.3 5.7 47.0 45.3 43.6 35.5 27.4 19.3
57 50.0 5.0 49.6 49.6 49.6 45.4 37.1 28.8 46.2 5.6 44.8 44.8 44.8 43.8 35.5 27.2
1750
77 61.2 5.3 40.5 30.0 19.6 - - - 54.7 5.9 38.6 27.7 16.9 - - -
72 58.1 5.2 46.8 38.2 29.6 21.0 - - 53.2 5.8 44.4 35.8 27.2 18.5 - -
67 54.9 5.2 53.2 46.4 39.6 30.5 21.4 - 51.5 5.7 50.2 43.8 37.5 28.3 19.1 -
62 53.4 5.1 52.3 51.0 49.7 40.0 30.4 20.8 49.8 5.7 48.5 48.1 47.8 38.1 28.4 18.6
57 51.9 5.1 51.3 51.3 51.3 49.6 39.4 29.3 48.0 5.6 46.7 46.7 46.7 46.7 37.6 27.3
2000
77 60.1 5.3 44.4 31.4 18.4 - - - 53.7 5.8 42.6 29.1 15.7 - - -
72 58.2 5.2 49.6 39.9 30.3 20.6 - - 53.3 5.7 47.0 37.4 27.8 18.2 - -
67 56.2 5.1 54.7 48.4 42.1 31.7 21.2 - 52.6 5.7 51.3 45.6 39.9 29.4 18.9 -
62 55.0 5.1 53.9 53.9 53.9 42.7 31.5 20.3 51.2 5.6 50.0 50.0 50.0 40.6 29.3 17.9
57 53.8 5.1 53.1 53.1 53.1 53.1 41.8 29.8 49.9 5.6 48.6 48.6 48.6 48.6 39.6 27.4
2250
72 58.3 5.2 52.3 41.6 30.9 20.2 - - 53.3 5.7 49.5 38.9 28.4 17.8 - -
67 57.5 5.1 56.2 50.4 44.5 32.8 21.1 - 53.7 5.6 52.4 47.4 42.3 30.5 18.7 -
62 56.6 5.1 55.5 55.5 55.5 45.4 32.6 19.8 52.7 5.6 51.5 51.5 51.5 43.2 30.2 17.2
57 55.7 5.1 54.8 54.8 54.8 54.8 44.1 30.3 51.8 5.6 50.5 50.5 50.5 50.5 41.7 27.5
2500
72 58.4 5.1 55.0 43.3 31.5 19.8 - - 53.4 5.6 - 40.5 29.0 17.5 - -
67 58.7 5.1 57.8 52.4 47.0 33.9 20.9 - 54.7 5.6 - 49.1 44.7 31.6 18.6 -
62 58.1 5.1 57.2 57.2 57.2 48.1 33.7 19.3 54.2 5.6 - 53.0 53.0 45.8 31.2 16.5
57 57.5 5.1 56.6 56.6 56.6 56.6 46.5 30.8 53.6 5.6 - 52.4 52.4 52.4 43.8 27.6
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBh = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT061 high speed compressor (5.0 ton) (continued)
Air on evaporator
coil
Temperature of air on condenser coil
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
CFM
WB
(°F)
Return dry bulb (°F) Return dry bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65