Johnson Controls Ducted Systems 77
Additional static resistance - ZT037 through 061
Size
(tons)
Model CFM Cooling only
1
1. Add these values to the available static resistance in the respective blower performance tables.
Economizer
2
3
2. Deduct these values from the available external static pressure shown in the respective blower performance tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit delivers less CFM during full economizer operation.
4-in. pleated filter
2
Electric heat kW
2
3 6 9 15 20 24
037 (3) ZT
900 0.05 -0.05 0.01 0.00 0.00 0.00 0.01 0.01 0.01
1000 0.05 -0.03 0.02 0.00 0.00 0.00 0.02 0.02 0.02
1100 0.04 -0.02 0.03 0.01 0.01 0.01 0.02 0.02 0.02
1200 0.04 0.00 0.04 0.01 0.01 0.01 0.02 0.02 0.02
1300 0.03 0.01 0.05 0.01 0.01 0.01 0.03 0.03 0.03
1400 0.03 0.03 0.07 0.02 0.02 0.02 0.03 0.03 0.03
1500 0.03 0.04 0.08 0.02 0.02 0.02 0.04 0.04 0.04
049 (4)
061 (5)
ZT
1200 -0.01 0.10 0.05 0.01 0.01 0.01 0.02 0.02 0.02
1300 -0.01 0.11 0.06 0.01 0.01 0.01 0.03 0.03 0.03
1400 -0.01 0.12 0.06 0.02 0.02 0.02 0.03 0.03 0.03
1500 -0.01 0.13 0.07 0.02 0.02 0.02 0.04 0.04 0.04
1600 -0.01 0.14 0.08 0.02 0.02 0.02 0.04 0.04 0.04
1700 -0.01 0.15 0.08 0.03 0.03 0.03 0.05 0.05 0.05
1800 -0.02 0.16 0.09 0.03 0.03 0.03 0.05 0.05 0.05
1900 -0.02 0.17 0.10 0.04 0.04 0.04 0.06 0.06 0.06
2000 -0.02 0.18 0.10 0.04 0.04 0.04 0.07 0.07 0.07
2100 -0.03 0.19 0.11 0.05 0.05 0.05 0.07 0.07 0.07
2200 -0.03 0.20 0.12 0.06 0.06 0.06 0.08 0.08 0.08
2300 -0.04 0.21 0.12 0.06 0.06 0.06 0.09 0.09 0.09
2400 -0.04 0.22 0.13 0.07 0.07 0.07 0.10 0.10 0.10
2500 -0.05 0.23 0.14 0.08 0.08 0.08 0.11 0.11 0.11
Additional static resistance - ZT078 through 150
Size (tons) Model CFM Cooling only
1
1. Add these values to the available static resistance in the respective blower performance tables.
Reheat coil
2 3
Economizer
2
3
2. Deduct these values from the available external static pressure shown in the respective blower performance tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is
less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
4-in. filter
2
Electric heat kW
2
09 18 24 36 54
078 (6.5)
090 (7.5)
102 (8.5)
120 (10)
150 (12.5)
ZT
1900 0.03 0.07 0.04 0.12 0.05 0.06 0.07 0.08 0.10
2100 0.04 0.08 0.10 0.13 0.06 0.07 0.08 0.09 0.11
2300 0.06 0.09 0.17 0.14 0.07 0.08 0.09 0.10 0.13
2500 0.08 0.10 0.23 0.16 0.08 0.09 0.10 0.11 0.14
2700 0.10 0.11 0.29 0.17 0.09 0.10 0.12 0.13 0.16
2900 0.12 0.12 0.34 0.19 0.10 0.11 0.13 0.14 0.18
3100 0.15 0.13 0.40 0.20 0.12 0.13 0.15 0.16 0.20
3300 0.17 0.14 0.45 0.22 0.13 0.14 0.17 0.18 0.22
3500 0.20 0.15 0.51 0.26 0.15 0.16 0.19 0.20 0.24
3700 0.22 0.17 0.56 0.27 0.17 0.18 0.21 0.22 0.26
3900 0.25 0.18 0.61 0.29 0.19 0.20 0.23 0.24 0.28
4100 0.28 0.19 0.66 0.32 0.21 0.22 0.25 0.26 0.31
4300 0.31 0.20 0.70 0.35 0.23 0.24 0.28 0.29 0.34
4500 0.34 0.21 0.75 0.38 0.25 0.26 0.30 0.31 0.37
4700 0.38 0.22 0.79 0.41 0.28 0.29 0.33 0.34 0.40
4900 0.41 0.24 0.83 0.44 0.30 0.31 0.35 0.37 0.43
5100 0.45 0.25 0.87 0.47 0.33 0.34 0.38 0.40 0.46
5300 0.48 0.26 0.91 0.51 0.35 0.37 0.41 0.43 0.49
5500 0.52 0.27 0.95 0.55 0.38 0.40 0.44 0.46 0.53
5700 0.56 0.28 0.98 0.58 0.41 0.43 0.47 0.49 0.56
5900 0.60 0.30 1.02 0.62 0.44 0.46 0.50 0.53 0.59
6100 0.64 0.31 1.05 0.67 0.47 0.49 0.53 0.56 0.62
6300 0.69 0.32 1.08 0.71 0.50 0.53 0.56 0.59 0.65