When I2 module installed in MIO slot, SP1 and SP2 can be switched by an external
switch. If the switch is off, SV=SP1; if the switch is on, SV=SP2.
Ramp Slope
limit (Only for
AI-526P)
Once SPr was set, if PV<SV when program start, the first step of ramp slope will
limited by SPr value until the temperature reach the first SV , under this limitation, the
RUN lamp will keep flashing.
For Ramp mode. SPr had effect on first step only.
For Soak mode, SPr had effect on each step.
No. of Program
step (Only for
AI-526P)
To define the number of program in use.
Pno= 0, disable the program running mode, then AI-526P will same as AI-526,
meanwhile, can set the parameter “SPr” to limit the ramp time.
Pno=1~30, AI-526P working as normal programmable controller