POWER FACTOR REGULATOR Controller
The Controller
/
PF regulators measure cosϕ in a supply system and control the connection and disconnection of capacitors to
obtain a target programmed value.
This manual is an easy guide for the use and operation of the
Controller
/
. For more information, the complete
manual can be downloaded from the web site of ZEZ SILKO
www.zez-silko.cz
Any manipulation or use of the equipment out of the conditions
specified by the manufacturer may put in risk the user safety. Before
any maintenance operation the equipment must be disconnected from power
supply. In case of miss operation or protection fault the equipment must be
disconnected from supply and remain out of service ensuring against any
accidental reconnection.
1.- Regulator Connection
For proper operation it’s necessary to install a current transformer, CT
(normally In / 5 A), which primary must be sized according to the
maximum expected load current in the installation.
The regulator supply (C-D terminals) must
phases and the CT should be located in the third phase. See technical
characteristics for cable sizes and required protections.
Must use an switch or automatic switch for supply the regulator
The current
transformer , CT,
must be located so that it
measures the whole load current
plus the correction capacitors
2.- TECHNICAL CHARACTERISTICS
Supply and V measurement input
terminals (C-D)
400 VAC - standard, 110, 230, 480 VAC-on request, +15%-10%
45-65 Hz, Connect preferably to phases L2-L3
Supply cables size and protection Cross section 1,5mm
2
; 0,5 to 2A Fuses gl type
Current measurement circuit
Current transformer (CT) , In /5 , Place preferably in phase L1
Minimum cabling cross section 2,5mm
2
Current measurement margin
0,1 to 5 A (maximum overload +20%)
Voltage and current :1%; cosϕ : 2% ± 1 dígit
Power consumptions
110V: 7 VA (no load) ; 8 VA(6 relays); 9,8 VA(12 relays)
230V: 7 VA (no load) ; 8 VA(6 relays); 9,6 VA(12 relays)
400V: 6 VA (no load) ; 7,5 VA(6 relays); 9,5 VA(12 relays)
480V: 7,8 VA (no load) ; 8,6 VA(6 relays); 10 VA(12 relays)
1 line x 3 digits x 7segments + 20 icons
Output Relay Contacts Max. 250 VAC, 10 A, AC1
Output Relay Cabling and
Protection
Cabling cross section 1,5mm
2
, Protection by means of a 6A
circuit breaker (C curve) or by a 6A fuse (gl type)
Alarm Output Relay Last relay automatically set as alarm output , if not in use
Compliant to the following
Standards
EN 61010, EN 61000-3-2, EN 61000-3-3, EN 50081-2, EN 50082-
1, EN 50082-2, EN 61000-4-2, EN 61000-4-4, EN 61000-4-8, EN
61000-4-5, EN 61000-4-11 , UL 94
Safety / Insulation Category III , Class II, According to EN 61010-1,
Environment limit conditions
Temperature limits: -20ºC a +60ºC; Relative Humidity 95%
(without condensation). Max. Altitude: 2000m
Protection degree
IP51 (panel mounted)
IP30 (regulator box) , According to EN-60529
FCP (Minimum number of operations)
3.- Four Quadrants Operation
The Controller
/
regulators operate in 4 quadrants (suitable
for imported or exported active power). For exported power, a negative
symbol is displayed in the cosϕ indication. Check phase connection and
setup if there is no exported energy and the indication is not correct (see 4.3,
SET-UP - phase)
0º
90º
180º
-90º
Imported Power
Exported Power
KW +
kVAr +
Leading/Capacitive
KW -
kVAr -
KW +
kVAr -
Lagging / Inductive
KW -
kVAr +
Cosϕ -
Lagging / Inductive
Cosϕ -
Cosϕ +
Cosϕ +
Leading/Capacitive
Display
Standard mode: Displays cosϕ
cosϕ Indication / setting
C/K setting. See paragraph 6
Program setting. See 4.2
Delay time setting for switching on/off operations
Nr of steps setting
Setting CT phase and polarity connection
- Cursor keys (when in setting mode)
- Manual ON / OFF (push during more than 1s when in RUN mode)
- Push both to see the Nr of connected steps
SETUP KEY: Push during more than 1s to enter SETUP mode
Lagging current indication (Inductive load)
Leading current indication (Capacitive load)