Zhejiang CHINT Instrument & Meter Co., Ltd. DTSU666 Series - Communication Protocols and Settings; Data Registers and Conversion

Default Icon
7 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
                     Quick operation manua 
Page 4/7 
Factory setting: DL/T 645-2007 protocol, Parity(E.1), Baud Rate(9600bps),Meter Address see
lable.
The RS485 communication supports DLT 645-2007 protocol or ModBus_RTU protocol, DLT
645-2007 supports read Meter Address, (current) total import active energy, (current) export active
energy, (current)quadrants reactive energy, (current)quadrants reactive energy,
(current)quadrants reactive energy, (current)quadrants reactive energy, voltage, current, active
power, reactive power, power factor,frequency.
ModBus_RTU protocol, Parity(n.2), Baud Rate(9600bps),Meter Address see lable.
Table 3 ModBus Register Address
Parameter
address
Parameter
code
Instruction of the
parameters
Type of data
Length
of data
Word
Read&write
attributes
Keyboard parametersdetailed function see the instruction of the programming parametersthe actual value
of the parameter with(*) communication parameter value × 0.1
0000H REV. version
signed int
1 R/W
0001H UCode
Programming password
codE
signed int 1 R/W
0002H ClrE
Electric energy zero
clearing CLr.E(1:zero
clearing)
signed int 1 R/W
0003H net
Selecting of the
connection mode
net(0:3P4W,13P3W)
signed int 1 R/W
0004H RESERVED reserved signed int 1 R/W
0005H RESERVED reserved signed int 1 R/W
0006H IrAt
Current Transformer
Ratio
signed int 1 R/W
0007H UrAt
Potential Transformer
Ratio(*)
signed int 1 R/W
000BH Meter type Meter type signed int 1 R
002CH Protocol Protocol changing-over signed int 1 R/W
002DH Addr
Communication address
Addr
signed int 1 R/W
002EH bAud
Communication baud rate
bAud
signed int 1 R/W
002FH Second Second signed int 1 R/W
0030H Minute Minute signed int 1 R/W
0031H Hour Hour signed int 1 R/W
0032H Day Day signed int 1 R/W
0033H
Month
Month
signed int
1
R/W
0034H Year Year signed int 1 R/W
Electric quantity of the secondary side
2000H Uab
Line -line voltage, the
unit is V(It is invalid for 3
Floating Inverse(AB CD) 2 R
2002H Ubc Floating Inverse(AB CD) 2 R