Model: SF-105 Digital Temperature Controller
Dimension:77(Length) 35(Width) 60(Depth)mm
Mounting hole dimension:71(Length) 29(Width)mm
× ×
×
0=Electric heater
1=Hot gas
0~40 /
above setpoint
40~0 /
below setpoint
0
1 90Min
60Min
F5
0=Parallel with comp.
1 = Continuous running
except defrost
Fan operating function
Defrost function
High temperature alarm
Low temperature alarm
Alarm time delay
F0
Parameter
Parameter
Function
Function
Set range
Set range
Default
Default
0 20
32 68
8
46
45
120
20
68
1 10
1 18
4
7
5 5
5 5
0= 1=
0
0
0
0
1 60Min
0 24Hr
20Min
6Hr
0
F1
F2
F3
F4
Set temp.
Set temp.
0 10Min
2Min
E1
E2
E3
E4
E5
E6
0=Normal display
1 = Last value
before defrost
Lower setpoint limit
Higher setpoint limit
Temp. hysteresis
Comp.start delay time
Offset on room temp.
Offset on evap. Temp.
Max. Defrost duration
Defrost interval time
Defrost termination temp.
Display during defrost
Temperature unit
C1
45
40
35
31
20
20
C2
C3
C4
Front Panel Operation
1 . Set temperature (compressor stop temperature) adjustment
Press button, the set temperature is displayed.
P o modify and store the displayed value , Press button to exit the and
display the cold room temperature.
If no more button is pressed within 6 seconds, the cold room temperature will be displayed.
(Set temperature adjustment range: parameter E1 E2)
2. Manual start/stop defrost: Press button and hold for 6 seconds to defrost or stop defrost.
3. Display the evap. Temperature : Press button and hold for 6 seconds, the evap. Temp. is displayed.,
After 6 seconds the cold room temp. is resumed to be displayed.
4. Refrigeration LED:During refrigeration,the LED is on;When the cold room temp. is constant,the LED is off;
During the delay start, the LED flashes.
5. Defrost LED: during defrosting, the LED is on; When it stops defrosting, the LED is off. During the delay
display of defrost, the LED flashes.
6. Parameter setup
Press button and hold for 6 seconds to enter the parameter setup mode while E1 flashes.
Press again button to select sequentially from the parameters : E2,E3,E4,E5,E6,F1,F2~C4.
Press or button, the value of parameter will be displayed and can be modified and stored.
If no more button is pressed within 6 seconds, it will return to normal operation mode.
ress or button t adjustment
Features of Function
Mini-sized and integrated intelligent control and applicable to the compressor of one HP.
Temperature Display/ Temperature Control/ Manual, automatic defrost by electric heater or hot gas
/Evap. Fan Control/High,Low temperature alarm/ Value Storing/ Self Testing /Parameter Locking
Specifications
1. Output of the outside sealed transformer:AC12V(one transformer matched with one temp. controller)
2. Temperature sensor: NTC, Double sensors(for cold-room temp.&defrost control),2m(L)
3. Range of temperature displayed : 5 45 ( 4
5 45 ( 4
1 ±
±
±
4 0~120 ); Accuracy: ( 2 )
4. Range of set temperature: 4 0~120 ); Factory default :0 ( 32 )
5. Temperature of the operating environment: 10 60 Relative Humidity:20%~90%(Non-condensing)
6. Output contact capacity:
Compressor: N.O. 20A/250VAC
(applicable to 1 HP Compressor,if more it needs to connect an AC contactor)
Defrost: N.O.10A/250VAC (applicable to 1KW load, if more it needs to connect an AC contactor)
Evap. Fan: N.O. 5A/250VAC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Zhongshan Shangfang Instrument Meter SF-105 and is the answer not in the manual?

Zhongshan Shangfang Instrument Meter SF-105 Specifications

General IconGeneral
ModelSF-105
CategoryTemperature Controller
Accuracy±0.5%FS
Operating Temperature0-50°C
Input TypeThermocouple
Control OutputRelay, SSR
DisplayLED
Power Supply50/60Hz