Characteristic 1 symbolises the decimal number 2, corresponding to the CAN-OPEN address 2
Characteristic 2 symbolises the decimal number 8, corresponding to the CAN-OPEN address 8
Characteristic 3 symbolises the decimal number 9, corresponding to the CAN-OPEN address 9
Possible LED codes
LED yellow LED red LED green Designation Validity
General
Off Off Off Defective module
Off on Off Red LED lights after reset once, for approx. 5 s
on on Off Hardware error, memory error continuously, in case of error
7x binary - - - - - - Bus address display continuously, if no hardware error
exists
fast flashing - - - - - - Invalid bus address (0) continuously, in case of error
1x - - - Off System clock error continuously, in case of error
2x - - - Off External oscillator error, device
runs with internal clock source
continuously, in case of error
3x - - - - - - I
2
C-Fehler as long as connection is faulty
CAN-OPEN specific
- - - - - - normal blink-
ing
Device on standby
- - - - - - on device in operation
- - - - - - 1x Stopped
Off 1x 2x Limit reached
Off on Off Device removed from bus
Off fast flashing fast flashing LSS (Layer Setting Services)
Off normal blink-
ing
- - - Invalid configuration
fast flashing cycle time = 300 ms corresponds to 150 ms pulse / 150 ms pause
binary blinking cycle time = 600 ms corresponds to 150 ms pulse / 450 ms pause
normal blinking cycle time = 600 ms corresponds to 300 ms pulse / 300 ms pause
- - - These LEDs can be ignored in the named combinations.
Operating Instructions AM-CAN-OPEN – model series Communication
L-BAL-E199-GB 1846 Index 005 Part.-No. 00163405-GB