TBL02_55-GB06/04 Part.-No. 00153239-GB
Page 41 / 105
IO Setup
F
¨
A Function (output 0-10 V)
1 A: constant voltage 10 V
2 A: proportional modulation
3 A: proportional signal E1
4 A: proportional signal E2
5 A: Group control
6 A: only 2.03 controller 2 (Cooling)
7 A: only 2.03 controller 2 (Heating)
¨
D1 / D2 Function (digitale inputs)
1 D: Enable ON/OFF
2 D: External fault
3 D: Limit ON/OFF
4 D: Switch over: Signal E1 / E2
5 D: Switch ofer Setpoint 1 / 2
6 D: Switchover: Internal / External
7 D: Controlling /Manual internal
8 D: Switch over: actualValue>Set=n+/n-
¨
K1 /K2 Function (Relay out)
1 K: Operaiting indication
2 K: Fault indication
3 K: external fault
4 K: Limit modulation
5 K: Limit E1
6 K: Limit E2
7 K: Setpoint Offset
8 K: Group control
9 K: only 2.03 heating function
10 K: only 2.03 cooling function
8.3.11 Factory setting and user setting for modes 2.01 - 2.05
Parameter Factory setting User
Setting
Setpoint 1 20 °C 5 °C 20° C 20° C 0.0 °C
Setpoint 2 -- -- -- -- --
Pband 5.0 K 20 K 5.0 K 5.0 K 5.0 K
Min. Speed 0 % 0 % 0 % 0 % 0 %
Max. Speed 100 % 100 % 100 % 100% 100 %
Manual mode OFF OFF OFF OFF OFF
Speed manual 100 % 100 % 100 % 100 % 100 %
Offset AnalogOut 0.0 K
Pband AnalogOut 2.0 K
Min. AnalogOut 0 %
Max. AnalogOut 100 %
OffsetDigitalOut -1.0 K
Hyst. DigitalOut 1.0 K
Alarm MinimumK2 0.0 °C
Setting
Alarm MaximumK2 40.0°C
Mode 2.01 2.02 2.03 2.04 2.05
E1 Analog IN TF.. TF.. TF.. TF.. TF..
E1 Min. ----- ----- ----- ------ -----
E1 Max. ----- ------ ------ ------ ------
E1 Decimal ----- ------ ------ ------ ------
E1 Unit ----- ------ ------ ------ ------
E1 Offset 0.0 K 0.0 K 0.0 K 0.0 K 0.0 K
E2 Function
OFF OFF OFF 4 E 5 E
E2 Analog IN ------ ----- ----- TF TF
E2 Min. ----- ----- ----- ----- -----
E2 Max. ----- ----- ----- ------ -----
E2 Decimal ------ ----- ----- ------ ------
E2 Unit ------ ----- ----- ------ ------
Base setup
E2 Offset ------ ----- ----- 0.0 K 0.0 K
PIN-Protection OFF OFF OFF OFF OFF
Set Protection OFF OFF OFF OFF OFF
Save user Setup OFF OFF OFF OFF OFF
Alarm Sensores OFF OFF OFF OFF OFF
Limit ----- ----- ----- ----- -----
Msco OFF OFF OFF OFF OFF
ON value Group2 ----- ----- ----- ----- ------
n-min atGroup2 ----- ----- ----- ----- -----
actVal > Set = n+ ON ON ON ON ON
Type of control PPPPP
KP 50% 50% 50% 50% 50%
KI 50% 50% 50% 50% 50%
KD 50% 50% 50% 50% 50%
TI 0 % 0% 0% 0% 0%
Controller Setup
A Function 1 A 1 A 6 A 1 A 1 A
A min 0.0 V 0.0 V 0.0 V 0.0 V 0.0 V
A max 10.0 V 10.0 V 10.0 V 10.0 V 10.0 V
A Inverting OFF OFF OFF OFF OFF
D1 Function OFF OFF OFF OFF OFF
D1 Inverting ----- ----- ----- ----- -----
D2 Function OFF OFF OFF OFF OFF
D2 Inverting ----- ----- ----- ----- -----
E1 Inverting OFF OFF OFF OFF OFF
E2 Inverting ----- ----- ----- OFF -----
K1 Function 1 K 1 K 2 K 1 K 1 K
K1 Inverting OFF OFF OFF OFF OFF
K2 Function 2 K 2 K 9 K 2 K 2 K
K2 Inverting OFF OFF OFF OFF OFF
IO Setup
BUS Address 247 247 247 247 247
2.01
Temperature control
2.022
Temperature control depending on
outdoor temperature
2.03
Temperature control with additional
functions (heating, shutter, temp.
monitoring)
2.04
Temperature control with 2 sensors.
-
comparison with control to higher
value.
- Average calculation of 2 measuring
places
2.05
Temperature control with 2 sensors,
regulation on differece
temperature
¨
E2 Function (Analog IN 2)
F
1 E: 0-10 V external Setpoint
2 E: external manual mode
3 E: Sensor average to E1
4 E: Sensor comparison to E1
5 E: Sensor difference to E1
6 E: Sensor for Setpoint lowering
(only for Mode 4.02 and 5.02)