Handbook Ucontrol type-lines PXDM Date 06/04
TBL02_55-GB06/04 Part.-No. 00153239-GB
Page 71 / 105
8.7.5 Factory setting and user setting for modes 6.01
Parameter Factory setting User
Setting
Setpoint 1 0.5 m/s
Setpoint 2 -----
Pband 0.5 m/s
Min. Speed 0 %
Max. Speed 100 %
Manual mode OFF
Speed manual 100 %
Setting
Mode 6.01
E1 Analog IN
0-1 MAL
E1 Min.
E1 Max. -----
E1 Decimal -----
E1 Unit -----
E1 Offset 0.0 m/s
E2 Function
OFF
E2 Analog IN -----
E2 Min. -----
E2 Max. ------
E2 Unit -----
E2 Unit -----
E2 Offset ------
Base setup
PIN-Protection OFF
Set Protection OFF
Save user Setup OFF
Alarm Sensors OFF
Limit -----
Msco OFF
ON value Group2 -----
n-min atGroup2 -----
actVal > Set = n+ OFF
Type of control PID
KP 50 %
KI 50 %
KD 50 %
TI 3 %
Controller Setup
A Function 1 A
A min 0.0V
A max 10.0 V
A Inverting OFF
D1 Function OFF
D1 Inverting --
D2 Function OFF
D2 Inverting --
E1 Inverting OFF
E2 Inverting --
K1 Function 1 K
K1 Inverting OFF
K2 Function 2 K
K2 Inverting OFF
IO Setup
BUS Address 247
6.01
Air velocity control
- Setpint in m/s
¨
E2 Function (Analog IN 2)
F
1 E: 0-10 V external Setpoint
2 E: external manual mode
3 E: Sensor average to E1
(only for mode 2.04 alternative)
4 E: Sensor comparison to E1
5 E: Sensor difference to E1
6 E: Sensor for Setpoint lowering
(only for Mode 4.02 and 5.02)
IO Setup F
¨
A Function (output 0-10 V)
1 A: constant voltage 10 V
2 A: proportional modulation
3 A: proportional signal E1
4 A: proportional signal E2
5 A: Group control
¨
D1 / D2 Function (digitale inputs)
1 D: Enable ON/OFF
2 D: External fault
3 D: Limit ON/OFF
4 D: Switch over: Signal E1 / E2
5 D: Switch ofer Setpoint 1 / 2
6 D: Switchover: Internal / External
7 D: Controlling /Manual internal
8 D: Switch over: actualValue>Set=n+/n-
K1 /K2 Function (Relay out)
1 K: Operaiting indication
2 K: Fault indication
3 K: external fault
4 K: Limit modulation
5 K: Limit E1
6 K: Limit E2
7 K: Setpoint Offset
8 K: Group control