Handbook Ucontrol type-lines PXDM Date 06/04
TBL02_55-GB06/04 Part.-No. 00153239-GB
Page 22 / 105
P ESC
7.2 Info
7.2.1 For mode speed controller 1.01
This menu group
serves INFORMATIONAL purposes only. Settings cannot be made here.
percent.
Internal controller output (modulation of the controller device)
In addition to the bar display, the approximate level of the output voltage while a load is
connected is displayed in.
If the output voltage is verified using a meter, the value measured at 20 % is considerably
higher than 20 % of the applied mains voltage. However, the speed of the motor approximately
corresponds to the speed at which the operation with a sinusoidal voltage of this level is
reached.
The switching-off of the motor voltage at a controlled variable under 15 % (back ON at a
controlled variable of 20%) is not discernable in the modulation display.
Display of the type and level of the active default signal in percent (0-100 % = 0-10 V,
10-0 V, 0-20 mA, 20-0 mA, 4-20 mA, 20-4 mA).
Display: the device operates at :
Set „External 1“ = Signal to terminal „E1“ and „GND“
Set „External 2“ = Signal to terminal „E2“ and „GND“
Set „Intern 1“ = Menu „Set intern 1“
Set „Intern 2“ = Menu „Set intern 2“
display
%
Setting signal
100
90
80
70
60
50
40
30
20
10
012345678910 0-10 V
10 9 8 7 6 5 4 3 2 1 0 10-0 V
0 2 4 6 8 10 12 14 16 18 20 0-20 mA
20 18 16 14 12 10 8 6 4 2 0 20-0 mA
4 5,6 7,2 8,8 10,4 12 13,6 15,2 16,8 18,4 20 4-20 mA
20 18,4 16,8 15,2 13,6 12 10,4 8,8 7,2 5,6 4 20-4 mA