Handbook Ucontrol type-lines PXDM Date 06/04
TBL02_55-GB06/04 Part.-No. 00153239-GB
Page 24 / 105
7.3 Events / malfunctions
Display and query of events and malfunctions
Events during operation can lead to a malfunctioning of the device. The last 10 (0-9) events and
malfunctions are stored in the „Events“ menu group (position „0“ = most recent event).
The device differentiates between 3 types of events:
Examples of
possible events
1. Messages with code Msg
Events for notification only (e.g. factory setting after a malfunction in the Eprom automatically
loaded, message not after loading the factory setting via PIN).
2. Alarms with code AL
Events during which the device automatically restarts operation after the cause of the
malfunction has been remedied (e.g. mains failure), or remains in operation (e.g. externally-
trunked centralized fault).
3.Error with code Err
Events that lead to a disconnection of the controlled output (e.g. excess motor temperature).
Restarting is only possible after a reset (locked).
A momentary pending alarm or error message is indicated by a blinking indicator and appears alternately with the
standard display. In addition, it is signaled via the 3-internal LED’s.
Examples of possible events and faults:
Designation
Display
Code
Display
LED
internal
Relais switches
Operation Fault
Cause
Reaction of Controller /
fault adjustment
Set defaults
AL
- - -
Fault in Eprom Works with defaults
External fault AL
- selectable
in
Controller
Setup
Motor protection
unit triggered
(signal contact at
digital input
unchanged /
check contactors
Line fault AL
yellow+red X X
Failure of a fuse of
or mains phase
switches on again automatically
when the voltage has been
restored /
guarantee mains supply
Overload AL
red flashes X X
Internal
temperature too
high
Overload
unit cuts out and automatically
on again when the unit has
cooled down again /
monitor the temperature in the
device. Monitor the cooling of
the device
EEP fault
AL
all
flash
X
fault EEP
EEP damaged
unit works with defaults
EEP Corruption
AL
all
flash
X
data incorrectly controller runs with the read
settings
Motor fault Err
red X
Interruption
“TK“-“TK“
Switch off /
Check motor then Reset
Sensor
malfunction 1
Sensor
malfunction 2
*
Msg
or
AL
yellow+
green
selectable
in Controller
Setup
selectable
in
Controller
Setup
Interruption / short
circuit in sensor
line, or sensor
actual values
outside the
measuring range
The device works with minimal
or maximum modulation
depending on whether there is
a short-circuit or an interruption,
and on the programmed mode
of operation.
Check sensor
)* dependent on programmed function
↓P ↑ ESC
↓ ↑
↓ ↑